Permit Number: T21CM01420
Parcel: 12404098A

Address:
947 N PARK AV -

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM01420
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2021 JGARCIA1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Provide Structural, Architectural, and Electrical drawings prepared by a professional registrant for any ans all modifications associated with the installation of the ATM machines.
03/03/2021 JGARCIA1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. Provide Structural, Architectural, and Electrical drawings prepared by a professional registrant for any ans all modifications associated with the installation of the ATM machines.
03/11/2021 JVINCEN1 FIRE REVIEW Approved
04/06/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM01420
947 N Park Ave
Chase Bank Tenant Improvement

TRANSMITTAL: April 6, 2021

This site is located in the C-1 zone (UDC 4.7.20). Financial Service is a permitted use in this zone (Table 4.8-4), subject to Use Specific Standards 4.9.4.L.1 & .3 and 4.9.13.O.

1. As modification to the exterior of the building is proposed Design Review is required per Main Gate overlay Section B-2.d.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
04/07/2021 MGAYOSS1 DESIGN PROFESSIONAL REVIEW Approved DATE: April 7, 2021
FROM: Rick Gonzalez, Architect (#26992)
COT On-Call Design Professional
RE: Submittal T21CM01420,
Chase Bank in Aspire 2
I have reviewed the Main Gate District Submittal Package for Chase Bank in
the Aspire 2 Building submitted April 2021 for the purpose of determining its
conformance with the Submittal Requirements of the MGD. I have checked the
submittal against the Requirements in the UDC Article 5.12.
Submittal Requirements Status
1. Identify proposal and why review is required. N/A Tenant
(land split, minor subdivision, major subdivision, Improvement in
compliance with HDZ, change of existing existing building
development plan, new development plan, condition
of annexation or rezoning)
2. Identify any existing case numbers N/A T.I. In existing
associated with the property. (Rezoning, building shell
Subdivisions, Board of Adjustment, etc.) Provide
supporting documentation, rezoning conditions, etc. Complete
3. Provide a copy of existing approved Site (with Pre-submittal
Plan, Development Plan/Package or Tentative Plat documents)
for re-subdivisions.
4. If new plan, place a north arrow on it with Complied
correct scale.
5. Provide the address, parcel number, N/A Tenant
location of the property or a map to identify the
subject lot. (A copy of the Plat Map from the Pima
County Assessor’s Office will help.)
6. Identify the last approved use for the Use unchanged, this is
property and the proposed use(s). an existing tenant
7. Show existing/proposed property lines, lots, Complete
dimensions, and total square footage of each.
8. If no plan is on file, new plan should show Part of Shell
the existing building(s), proposed expansion(s) Submittal (N/A)
if applicable, gross floor area, and distance to all
property lines for each structure.
9. Identify the height of each new structure N/A
and/or expansion.
10. If your project is a bar, social organization, N/A
worship use, civic use, or restaurant, provide a fully
dimensioned floor plan, identifying the use of each
area or room.
11. Identify the existing zoning on the property, Part of shell approval
and adjacent zoning in all directions.
12. Provide height of outside walls closest to Part of shell approval
property lines of all existing/proposed buildings.
13. Show existing & proposed, dimensioned: Complete
parking spaces, driveways, site entrance/exit points.
14. Show refuse collection provisions with Part of Shell approval
adequate ingress/egress. plan
15. Identify pavement, curb, and sidewalk Complete
locations for all property frontages in the public
Right Of Way (ROW).
16. Show existing/proposed landscaping, fences, Shown on Shell plans
walls, and current/future ROW.
17. Indicate Federal Emergency Management Area N/A part of Shell
(FEMA) or city Flood Hazard designated areas.
18. Show proposed location of new sewer lines and N/A part of shell
connections to main.
General Comments
1. Parking in the shell building reserved for Chase Bank indicated in Submittal.
2. Car stacking addressed beyond 3 stacked spaces. Signage indicates to keep the
sidewalk clear
3. Double to single Storefront... I see no problem with this alteration or the
elevations in general.
2. Consideration of Shell Building drop off/pick-up and circulation between
vehicles and pedestrian relative to the drive-through teller service has been taken
into consideration. Information of flow patterns and how potential safety conflicts
may be eliminated has been adequately indicated.
I recommend approval as submitted.
Sincerely,
Rick Gonzalez, Architect
RGA
04/09/2021 LOREN MAKUS ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
04/13/2021 IMONSHI1 OUT TO CUSTOMER Completed