| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/09/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Coordinate the site plan with the description of the apartments included in the scope of work. 2.The HVAC heating/cooling load calculations (both copies) do not appear to be related to the heat pump schedule. 3. The heat pump schedule needs clarification. Why is the specified unit cooling capacity less than half of the cooling load calculation? Why is the heat pump tied to the exhaust fan operation? Why is an economizer being provided? How can the equipment curb be existing if the previous equipment was an evaporative cooler? |
| 03/09/2020 | LSHAMIS1 | ZONING | REVIEW | Approved | |
| 03/09/2020 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Provide structural calculations for roof mounted HVAC . Respond to plan review comments in writting . |
| 03/09/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan recommends. Also provide a written response. 1. Provide a complete panel schedule including load calcs for all equipment including the RTU. 2. Is the bathroom exhaust fan new? If so, provide sequence of operation or control. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |