Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T20CM01526
Parcel: 12315031B

Address:
715 E LEE ST

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T20CM01526
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/09/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Coordinate the site plan with the description of the apartments included in the scope of work.
2.The HVAC heating/cooling load calculations (both copies) do not appear to be related to the heat pump schedule.
3. The heat pump schedule needs clarification. Why is the specified unit cooling capacity less than half of the cooling load calculation? Why is the heat pump tied to the exhaust fan operation? Why is an economizer being provided? How can the equipment curb be existing if the previous equipment was an evaporative cooler?
03/09/2020 LSHAMIS1 ZONING REVIEW Approved
03/09/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change Provide structural calculations for roof mounted HVAC .


Respond to plan review comments in writting .
03/09/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan recommends. Also provide a written response.
1. Provide a complete panel schedule including load calcs for all equipment including the RTU.
2. Is the bathroom exhaust fan new? If so, provide sequence of operation or control.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.