Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/28/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide HVAC heating/cooling load calculations for AC-3 |
01/28/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Clarify the gas piping design. Is it a 2 PSIG system or a 7" WG system? Is the total developed length 150 feet or 300 feet? Is the branch pipe to AC-5 2" or 1-1/2"? |
01/28/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide compliance with NEC 440.14 for the new AC disconnect location on the roof. 2. Verify that there is a 120 volt GFI protected maintenance receptacle on the roof as required per NEC 210 for the maintenance of mechanical equipment. If not, Please provide. Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |