Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM00524
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/28/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide HVAC heating/cooling load calculations for AC-3 |
| 01/28/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Clarify the gas piping design. Is it a 2 PSIG system or a 7" WG system? Is the total developed length 150 feet or 300 feet? Is the branch pipe to AC-5 2" or 1-1/2"? |
| 01/28/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide compliance with NEC 440.14 for the new AC disconnect location on the roof. 2. Verify that there is a 120 volt GFI protected maintenance receptacle on the roof as required per NEC 210 for the maintenance of mechanical equipment. If not, Please provide. Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/05/2020 | SBORZAK1 | REJECT SHELF | Completed |
| 01/28/2020 | SBORZAK1 | OUT TO CUSTOMER | Completed |