Permit Number: T20BU00243
Parcel: 13213078B

Address:
1740 E 36TH ST

Review Status: Completed

Review Details: WALLS

Permit Number - T20BU00243
Review Name: WALLS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/15/2020 ANDREW CONNOR NPPO REVIEW Passed
08/10/2020 STEVE SHIELDS ZONING REVIEW Approved
08/19/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet LA-203; Details 1 and 2: These details do not match the Detail 1 on Sheet S02. Since the LA sheet is part of the structural calculation package, the details should be consistent. Please revise as required.
2. General: Please provide a project valuation for the labor and materials.
3. General: Please provide a Special Inspection Certificate with Parts A and B completed. This form may be found at www.tucsonaz.gov/PDSD.
08/24/2020 JOHN VAN WINKLE ENGINEERING REVIEW Approved