Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T19CM08973
Parcel: 124050590

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM08973
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2020 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
04/23/2020 KROBLES1 FIRE REVIEW Needs Review
12/19/2019 SARAH MEGGISON ZONING REVIEW Approved
12/19/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
12/19/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
12/19/2019 SMEGGIS1 ENGINEERING REVIEW Passed
12/19/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1; Floor Plan: Per the IBC Section 1109.11, 5% of the total seating and standing spaces must be accessible. The two ADA seating locations do not meet that requirement. Please verify and indicate the calculation on this sheet.
2. Sheet A1; Floor Plan: The north wall of Corridor 108 should be a one hour fire resistant rated wall since it is part of the corridor. Please verify.
3. Sheet A2; Reflected Ceiling Plan: A note at the walk-in cooler indicates a one hour fire rated ceiling. Please verify and indicate a U.L. Listing # for that assembly.
4. Sheet A3; Partition Details 1 and 2: For fire resistant rated partitions, please indicate a U.L. Listing #.
5. Sheet A3; Toilet Room Mounting Heights: Please indicate a dimension from the floor to the vertical grab bar per the ICC/ANSI Figure 604.5.1.
6. General: Please provide written responses to all review comments.
12/19/2019 ROBERT SHERRY WATER REVIEW Completed
12/19/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed