Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T19CM05218
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/08/2020 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Response letter indicates fire pump will be separated from the rest of the buidling by a 1 hour fire wall. Per section 913.2.1 of the 2018 International Building Code, a 2 hour wall is required. Please revise and clearly indicate on plans. |
| 01/08/2020 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Approved | |
| 01/09/2020 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | FROM: Steve Shields PDSD Zoning Review Section PROJECT: T19CM05218 - Residential Use Group / Student Housing Building Plan Review (2nd Review) Related to DP19-0059 MGD-19-01/T19SA00088 947 N. Park Avenue - C-1 to UC-1 Zoning (Maingate) TRANSMITTAL DATE: January 9, 2020 DUE DATE: January 6, 2020 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has reviewed the Building plans for compliance with the approved development package. While the building plans are consistent with the approved DP as it relates to the zoning review purview (Building footprint, Height, square footage, site conditions etc) zoning cannot approve the building plans until the 3rd Party and PDSD Commercial Plans reviewers have approved the building plans. In addition, the plans must be reviewed by Staff and the Design Professional for compliance with the Maingate regulations and conditions of the MGD-19-01 application and PDP. 2. COMMENT: Zoning will review the building plans on the next submittal to assure that any revisions made to the building plans do not affect zoning requirements. 3. COMMENT: Once the plans have been approved by the Design Professional, 3rd Party and PDSD Commercial Plans reviewers and no site changes are made that affect zoning requirements, zoning will stamp and sign the building plans as it pertains to the zoning review purview. If you have any questions about this transmittal, Contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: |
| 02/21/2020 | NROSS1 | DESIGN PROFESSIONAL | REVIEW | Reqs Change | |
| 12/31/2019 | ROBERT SHERRY | WATER | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/09/2020 | PMARTIN1 | OUT TO CUSTOMER | Completed |