Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S2.0 (Structural Layout); Structural Calculations (Page 15): The purlin call-out on the plan indicates a 100S300-54, while the calculations indicate 1000S300-54. Please coordinate.
2. Sheet S2.0; Structural Layout: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the purlin call-out on the plan.
3. Sheet S2.0; Structural Layout: Keynote 2 was not located on the plan. Please verify.
4. Sheet S2.0; Drilled Pier Footing Schedule: The schedule indicates the depth of the drilled pier as 12'-6" below finished grade, while the calculation (Page 24) indicates a minimum required depth of 13'-0". Please coordinate.
5. Sheet S3.0; Detail 201: Note 6 was not located on the detail. Please verify.
6. General: Please provide the Special Inspection Certificate with Parts A and B completed.
7. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
07/18/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved