The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T19CM03789
Parcel: 12404098A

Address:
947 N PARK AV

Review Status: Completed

Review Details: 3RD PARTY REVIEW - COMMERCIAL TI

Permit Number - T19CM03789
Review Name: 3RD PARTY REVIEW - COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/24/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change 1) Engineering will approve the building plans once all outstanding commercial and structural reviews have been completed
07/24/2019 ROBERT SHERRY WATER REVIEW Reqs Change 1. Coordinate the domestic water supply to the building with the civil engineers. The current site plan shows a 4" water meter and 6" domestic water line entering the building off 1st Street.
2. Provide the proposed water demand and fixture count for the building to verify the size of the water meter.
07/24/2019 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T19CM03789 - Tucson Student Housing 2.0 - Foundation only for Future 8-storey Building
Building Plan Review (1st Review) Related to DP19-0059
947 N. Park Avenue - C-1 Zoning

TRANSMITTAL DATE: July 24, 2019

DUE DATE: was not available at time of this review.

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has done a review of the foundation plans but cannot approve the plans at this time. While the foundation plans are consistent with the building footprint approved in development package zoning cannot approve the plans until the plans are approved by the 3rd Party Structural plans reviewers.

2. COMMENT: Zoning will review the building plans on the next submittal and do a comparison to the DP again to assure that the foundation plans are consistent with the approved DP and approve the plans once the 3rd Party plans reviewers also have approved the foundation plans.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Building foundation plans Level 1, and Levels B-1 and B-2
07/26/2019 MASHFOR1 FIRE REVIEW Approved
08/02/2019 PMARTIN1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/02/2019 STANTEC 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/19/2019 PMARTIN1 OUT TO CUSTOMER Completed
08/19/2019 QJONES1 REJECT SHELF Completed