Permit Number: T19CM01353
Parcel: 128100570

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T19CM01353
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2019 MARTIN BROWN FIRE REVIEW Approved
05/29/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/03/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Comment not resolved. Provide a detail showing how the spring isolators and all-thread rods are connected to the building structure itself. [Initial comment: Provide structural details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2018.]
2. The summary of the ventilation calculations does not indicate how the outside air quantities were determined. Show the rest of the calculations for the air handlers serving multiple zones. [Initial comment: Provide calculations to show how adequate ventilation will be provided for the occupied spaces. Reference: Section 401.2, IMC 2018.]
3. Removing the exhaust fans from the prep areas does not eliminate the exhaust requirement. Each prep room has four microwave ovens for a total required exhaust airflow rate of 280 cfm. [Initial comment: Cooking appliances that do not require the installation of a Type II hood (e.g. microwave ovens) shall be exhausted at a flow rate of 0.70 CFM per square foot; each appliance shall be assumed to occupy a space of not less than 100-square feet. Reference: Section 507.3, IMC 2012.]
06/03/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Sheets P2.02.A, P2.02.B and P2.02.C show primary roof drains terminating at the building wall over sidewalks. The development plans call for the primary roof drains to connect top scuppers under the sidewalks. Coordinate the development plans and the plumbing plans.
06/03/2019 ROBERT SHERRY WATER REVIEW Reqs Change 1. Comment not resolved. An approved development plan is not to be used for construction or modification of on-site utilities (e.g. water service to buildings, building sewers, site lighting, electrical service to buildings, etc.). The civil utility drawings are an integral part of the building permit. [Initial comment: The civil utility plan indicates the installation of a 2" water meter to serve the building water demand. Based on the water fixture units shown in Appendix E, IPC 2018, the water demand for the building will be about 137 GPM without considering the continuous demand from hose bibbs, make-up water for mechanical systems, and deionized water production. Tucson Water limits 2" water meters to a maximum demand of 120 GPM. Verify the total water demand for the building (including the demand contribution of non-plumbing uses) and revise the size of the water meter if needed.]
2. Comment not resolved; see comment 1. [Initial comment: The civil utility plan shows a 3" domestic water line terminating at the garbage area with a 1" domestic water line serving the building. Correct the civil plan to coordinate with the plumbing site plan.]
06/17/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Plan Sheet E9.06. Provide Energy calcs per the 2016 ASHREA 90.1, not the 2013. See COMcheck.
2. Ref; 2012 Tucson/Pima County Outdoor Lighting Code.
(a) Plan Sheet E1.01. The lumen calcs show 175000 total allowed SHIELDED lumens per acre. Please revise this to state 164000, per Table 401.1- E3 Option 3, Total full cut off plus unshielded = 175000 lumens allowed per acre. 175000 - 11000 (unshielded) = 164000 allowed full cut off per acre, (OLC). Please clarify.
(b)Provide a note requiring a special inspection for outdoor lighting as required per section 104.2.2, 106.2.1, (OLC).
(c) Could not locate the 16 'SL2' luminaires listed in the lumen calcs for un-shielded luminaires.
(d) Provide manufacture cut sheets for the exterior luminaires to verify shielding requirements. Section 104.2(2). Or include shielding information on the light fixture schedules.
(e) Provide battery back-up information for the exterior lighting controls as required per section 403.5.1.
3. REf; Plan Sheet E704, Elertical Service Grounding Detail. Provide bonding conductors sized per art 250.104, 250.102C(1), NEC for Metal Water Piping, Structural Steel, or other Metal Piping.
Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2016 ASHREA, 2012 Tucson/Pima County Outdoor Lighting Code, (OLC).
06/18/2019 LOREN MAKUS ENGINEERING REVIEW Needs Review DP18-0301 must be approved first.
06/19/2019 DAVID RIVERA ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: David RIvera
Zoning Review

PROJECT: Texas Instruments
T19CM01353 - Related to DP18-0301
Building Plan (1st Review)

TRANSMITTAL DATE: June 19, 2019

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The building plans have been reviewed for compliance with development package DP18-0301 and although it appears that the building plans match the development package Zoning cannot approve the building plans until the development package has been approved.

3. Until all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956