Permit Number: T19CM01193
Parcel: 12404097C

Address:
950 N TYNDALL AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM01193
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The load calculations for FC-3/CU-3 and FC-4/CU-4 do not support the specified capacities. [Initial comment: The heating/ cooling load calculations do not support the specified capacities of the HVAC systems. The load calculations do not include FC-4/CU-4.]
2. Comment not addressed. Note: verify the EER and SEER values for the split systems. [Initial comment: The specified fan coil units are not "field-assembled DX systems", correct the COMcheck component descriptions.]

Final Status

Task End Date Reviewer's Name Type of Review Description
03/28/2019 QJONES1 APPROVAL SHELF Completed
03/28/2019 QJONES1 OUT TO CUSTOMER Completed
03/28/2019 QJONES1 REJECT SHELF Completed