Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM01193
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/15/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The load calculations for FC-3/CU-3 and FC-4/CU-4 do not support the specified capacities. [Initial comment: The heating/ cooling load calculations do not support the specified capacities of the HVAC systems. The load calculations do not include FC-4/CU-4.] 2. Comment not addressed. Note: verify the EER and SEER values for the split systems. [Initial comment: The specified fan coil units are not "field-assembled DX systems", correct the COMcheck component descriptions.] |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/28/2019 | QJONES1 | APPROVAL SHELF | Completed |
03/28/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
03/28/2019 | QJONES1 | REJECT SHELF | Completed |