Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM01193
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/06/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
03/06/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1.Show how thefan coi units are connected to the building structure. 2. The heating/ cooling load calculations do not support the specified capacities of the HVAC systems. The load calculations do not include FC-4/CU-4. 3. Show how the requirements of C406, IECC 2018 are being addressed. 4. If the fan coil units areto be located above a ceiling, show where the secondary condensate drain will be terminated. The specified fan coil units are not "field-assembled DX systems", corect the COMcheck component descriptions. |