Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM01193
Parcel: 12404097C

Address:
950 N TYNDALL AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM01193
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/06/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/06/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1.Show how thefan coi units are connected to the building structure.
2. The heating/ cooling load calculations do not support the specified capacities of the HVAC systems. The load calculations do not include FC-4/CU-4.
3. Show how the requirements of C406, IECC 2018 are being addressed.
4. If the fan coil units areto be located above a ceiling, show where the secondary condensate drain will be terminated.
The specified fan coil units are not "field-assembled DX systems", corect the COMcheck component descriptions.