Permit Number: T19CM01193
Parcel: 12404097C

Address:
950 N TYNDALL AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM01193
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2019 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide written responses to all plan review comments:
1. Provide available arc fault current calculations and documentation for all new electrical service equipment. Show panel bracing requirements for new service panels. NEC 110.24
2. Provide maintenance outlet(s) for mechanical equipment at roof top locations and condensers.
3. Provide an electrical legent of all sysbols and abbreviations used on the electrical plan. IBC 107.2.1
02/19/2019 GPERU1 MECHANICAL-COMMERCIAL REVIEW Reqs Change Please provide written responses to all plan review comments.
1. Please indicate all existing and new equipment covered under the scope of the permit.
2. M-1 For new field coil units, load calculations shall be required for proper sizing of all equipment. Heating and cooling system design loads for sizing systems, appliances and equipment shall be determined in accordance with ASHRAE/ACCA Standard 183.
3. Cite all applicable and adopted codes for the basis of design for all mechanical and electrical equipment. IBC 107.2.1
4. Mechanical systems shall be designed to comply with Sections C403.2.1 and C403.2.2. Show compliance with the Mandatory system design requirements of the 2018 IECC.
5. Provide the building occupancy classifications, type of construction and occupant loads for all rooms, areas or spaces that will be serviced by new mechanical systems.
6. Identify the drain termination fixture for the condensate drain pipe. IPC 307.2.1
7. Provide the UL listed assembly for the penetrations in the mechanical room wall. Specify the fire resistive rating for the wall assembly. IBC 107.2.1

Final Status

Task End Date Reviewer's Name Type of Review Description
03/06/2019 QJONES1 APPROVAL SHELF Completed
03/06/2019 QJONES1 OUT TO CUSTOMER Completed
03/06/2019 QJONES1 REJECT SHELF Completed