Review Details: 3RD PARTY REVIEW - COMMERCIAL TI

Permit Number - T18CM09798
Review Name: 3RD PARTY REVIEW - COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2019 MARTIN BROWN FIRE REVIEW Approved Per M. Ashford, 12/20/18
01/14/2019 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size of the water meter for this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2012.
01/16/2019 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T18CM09798 - Civic/Education Use - Salpointe High School
Building Plan Review (1st Review) - Related to DP18-0282
1545 E. Copper Street - PAD 17 Zoning

TRANSMITTAL DATE: January 16, 2018

DUE DATE: January 17, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the Building plans for compliance with the unapproved version of the development package. While the building footprint and the site revisions are consistent with the unapproved version of the DP as it relates to the zoning review purview (Building footprint, Height, square footage, site conditions etc.) zoning cannot approve the building plans until the 3rd Party Commercial Plans Reviewers have approved the building plans.


2. COMMENT: If available, include a reference copy of the PDSD approved and signed version of the DP with the next submittal of the building plans package.


3. COMMENT: Zoning will review the building plans on the next submittal to assure that any revisions made to the building plans do not affect zoning requirements and the 3rd Party Commercial Plans Reviewers have also approved the building plans.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: as noted above
01/22/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change 1) Once the DP has been approved and any outstanding commercial review comments have been addressed, Engineering can conduct an over the counter review of the building plans. Call or Email to Schedule
2) Coordinate with Development Package (DP) to ensure that roof drains scupper underneath sidewalks. Reference City of Tucson Technical Standards Manual (TSM) section 7-01.4.1.E

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
01/25/2019 STANTEC 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
01/25/2019 KROBLES1 OUT TO CUSTOMER Completed