Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T18CM06810
Parcel: 13819032B

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T18CM06810
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/04/2018 JVINCEN1 FIRE REVIEW Approved
09/11/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Provide structural calculations for the 8 ft. CMU wall. IBC 107.2.1
2. Submit a geotechnical soils report as referenced in the structural calculations. 1603.1.6 IBC
09/12/2018 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. Provide an automatic transfer switch for transferring power to the generator; show on one-lind diagram. Provide verification of compliance with NEC 702.
09/14/2018 LOREN MAKUS ENGINEERING REVIEW Approved
09/18/2018 KROBLES1 COMMUNICATIONS REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/19/2018 SVALENZ1 OUT TO CUSTOMER Completed