Permit Number: T18CM04807
Parcel: 14029196A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM04807
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/26/2018 MARTIN BROWN FIRE REVIEW Approved
07/09/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet PV-1.0; Site Plan: Please provide dimensions on the plan indicating the distance from the new structures to property lines, to existing buildings/structures, and to the other new structures.
2. Special Inspection Certificate: Under the "Special Inspector" heading, please indicate the name of the ICC certified individual for each special inspection.
3. Sheet PV-1.0; Project Information: Please indicate on the sheet the occupancy classification and construction type for this project.
07/12/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide in detail the wiring methods prescribed for the removal of the existing wiring to the light poles that are to be removed, and continuation of the lighting branch circuit incorporated into the new canopy lighting.
Re;f 2012 IBC sec 107.2.1, 2011 NEC

Final Status

Task End Date Reviewer's Name Type of Review Description
08/09/2018 AVAUGHN1 OUT TO CUSTOMER Completed
08/09/2018 AVAUGHN1 REJECT SHELF Completed