Permit Number: T18BU00321
Parcel: 12404097C

Address:
950 N TYNDALL AV

Review Status: Completed

Review Details: POOL - COMM MODEL

Permit Number - T18BU00321
Review Name: POOL - COMM MODEL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/08/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/13/2018 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T18BU00321 - Tucson Student Housing Pool
Building plans (1st Review)
950 N. Tyndall Avenue

TRANSMITTAL DATE: June 13, 2018

DUE DATE: June 22, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the building plans but cannot approve them at this time. Due to the building's location within the Main Gate Overlay area, the proposed Pool Application must first be reviewed and approved by the Design Professional prior to approval by zoning.

2. COMMENT: In addition, the building plans must be approved by the PDSD commercial plans reviewers before zoning can approve the plans.

3. COMMENT: Once the plans have been approved by all Commercial Plans reviewers and no site changes are made that affect zoning requirements, zoning will stamp and sign the building plans as it pertains to the zoning review purview.

4. COMMENT: If the Design Professional approves the plans with conditions, the plan must be revised to incorporate those conditions.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email at David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
06/15/2018 CLAURIE1 DESIGN PROFESSIONAL REVIEW Approved Minor changes noted in the review, the Design Professional found them to be within acceptable limits of the design.
06/20/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/22/2018 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change T18BU00321

1) Building plans show a floor drain in the pool maintenance room; however the floor drain does not appear to be connected to a sanitary line. Confirm in writing that Detail 6 on sheet SP-503 runs to a sanitary sewer line. Engineering will conduct an over the counter review/approval for this comment when the response is provided

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007