Permit Number: T18BU00321
Parcel: 12404097C

Address:
950 N TYNDALL AV

Review Status: Completed

Review Details: POOL - SPA

Permit Number - T18BU00321
Review Name: POOL - SPA
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2018 MMORENO1 ENGINEERING REVIEW Needs Review
05/23/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Clarify the capacities of the pool and spa heater - shown as 299,999 BTUH and 400,000 BTUH.
2.Provide reference drawings showing the installation of the gas service and the drain within the pool equipment room.
05/23/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Could not verify Outdoor Lighting Code compliance. Information not provided with this submittal. Could not locate Lumen calcs as stated on the electrical plan.
Ref; 2012 IBC sec 107.2.1, Outdoor Lighting Code.
05/23/2018 MMORENO1 ZONING REVIEW Needs Review
05/24/2018 ARUIZ1 DESIGN PROFESSIONAL REVIEW Needs Review
05/24/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved