| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/23/2018 | MMORENO1 | ENGINEERING | REVIEW | Needs Review | |
| 05/23/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the capacities of the pool and spa heater - shown as 299,999 BTUH and 400,000 BTUH. 2.Provide reference drawings showing the installation of the gas service and the drain within the pool equipment room. |
| 05/23/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Could not verify Outdoor Lighting Code compliance. Information not provided with this submittal. Could not locate Lumen calcs as stated on the electrical plan. Ref; 2012 IBC sec 107.2.1, Outdoor Lighting Code. |
| 05/23/2018 | MMORENO1 | ZONING | REVIEW | Needs Review | |
| 05/24/2018 | ARUIZ1 | DESIGN PROFESSIONAL | REVIEW | Needs Review | |
| 05/24/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |