Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T17CM04762
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/20/2017 | TPROBAS1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/20/2017 | TPROBAS1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
06/20/2017 | ACONNOR1 | ENGINEERING | REVIEW | Passed | |
06/20/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | . Please address the following electrical plan review comments. Also provide a written response. #1. The grounding electrode conductor should be sized per 250.66 NEC. #2. #2. Provide load calcs for the service to verify the 250 kcmil riser conductors are sized properly. 250 kcmil conductors are rated at 255 amps per table 310.15B, and the service equipment shown on the riser diagram is rated at 400 amps, 2 load main circuit breakers rated at 200 amps each. #3. Provide the conduit, conductor, sizes and types and identify the load feeders designations. Ref: 2012 IBC sec 107.2.1, 2011 NEC. City of Tucson Commercial Plan Submittal Requirements |
06/20/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
06/20/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/29/2017 | MMENDIB1 | OUT TO CUSTOMER | Completed |