Permit Number: T17CM04762
Parcel: 11720015A

Address:
111 S CHURCH AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T17CM04762
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2017 TPROBAS1 BUILDING-COMMERCIAL REVIEW Approved
06/20/2017 TPROBAS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
06/20/2017 ACONNOR1 ENGINEERING REVIEW Passed
06/20/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change . Please address the following electrical plan review comments. Also provide a written response.
#1. The grounding electrode conductor should be sized per 250.66 NEC. #2.
#2. Provide load calcs for the service to verify the 250 kcmil riser conductors are sized properly. 250 kcmil conductors are rated at 255 amps per table 310.15B, and the service equipment shown on the riser diagram is rated at 400 amps, 2 load main circuit breakers rated at 200 amps each.
#3. Provide the conduit, conductor, sizes and types and identify the load feeders designations.
Ref: 2012 IBC sec 107.2.1, 2011 NEC. City of Tucson Commercial Plan Submittal Requirements
06/20/2017 MARTIN BROWN FIRE REVIEW Approved
06/20/2017 ANDREW CONNOR ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/29/2017 MMENDIB1 OUT TO CUSTOMER Completed