Permit Number: T17CM00366
Parcel: 11720015A

Address:
111 S CHURCH AV

Review Status: Completed

Review Details: 3RD PARTY REVIEW - COMMERCIAL

Permit Number - T17CM00366
Review Name: 3RD PARTY REVIEW - COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2017 KEN BROUILLETTE FIRE REVIEW Approved
02/08/2017 ROBERT SHERRY WATER REVIEW Reqs Change Clarify the water service to the building. Sheet P1.1.1 shows a 2" meter with a 3" RP and a 1-1/2" meter with a 2-1/2" water meter. Sheet P2.1, however, calls out a 3" water meter with a 4" RP serving floors 4, 5, 6, and 7; and a 1-1/2" meter with a 2-1/2" RP serving floors 1, 2, and 3.
02/09/2017 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: Marist on Cathedral Square
T17CM00366
Building Plan (1st Review)

TRANSMITTAL DATE: February 9, 2017

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Until development package DP15-0196 is fully approved the building plans cannot be approved.

3. The development package sheets provided in the building plan set either need to be the approved development package sheets or each sheet marked for reference only or removed from the plan set.

4. It appears that there are shade canopies that encroach into the right of way along Church Avenue. Some type of easement or agreement is required for this encroachment. Contact COT Real Estate to secure the easement or agreement. The easement or agreement will need to be secured prior to approval of the building plans.

5. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
02/09/2017 SSHIELD1 ZONING HC REVIEW Passed
02/15/2017 KLEE1 DESIGN PROFESSIONAL REVIEW Approved DATE: 2/13/17
FROM: Rick Gonzalez, Architect, City of Tucson On-Call Design Professional
TO: Carolyn Laurie, Planning and Development Services Department
RE: Design Professional Elevation review comments for Marist College
IID-15-11

The following review comments are provided with regard to the elevation changes made on the Approved Design Package submitted to PDSD on October 2016. The Design Professional is recommending approval the currently submitted revised renderings (1275 Marist Midrise - 20170207 Perspective Views - four pages).
1. Exterior NW Corner; upper level at entry corner - fenestration increased from approved design. Positive revision, add to approved design package.

2. Exterior SW Corner perspective varies from
02/21/2017 STANTEC 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Approved
02/21/2017 FRODRIG2 WWM REVIEW Needs Review
02/21/2017 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/21/2017 FERNE RODRIGUEZ OUT TO CUSTOMER Completed