Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM07023
Parcel: 12404098A

Address:
947 N PARK AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T16CM07023
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2016 MARTIN BROWN FIRE REVIEW Approved
09/26/2016 STEVE SHIELDS ZONING REVIEW Approved
10/11/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET AS0.5; ISLAND ATM PLAN: A SECTION CUT REFERENCES 2/AS1.2. PLEASE REVISE THE REFERENCE.
2. SHEET AS0.5; DETAILS 2 AND 3: THE 12" DIAMETER CONCRETE PIER NOTE SHOULD POINT TO THE PIER. PLEASE REVISE.
3. CHASE DRAWINGS (SHEET 11); GF GROUP STRUCTURAL DRAWINGS (SHEET S1): THE WIDTH OF THE ATM FOUNDATION IS NOT THE SAME ON THE CHASE DRAWING (4'-3") AND THE GF GROUP DRAWING (4'-1"). PLEASE COORDINATE.
4. GENERAL: THE STRUCTURAL CALCULATIONS FOR THE CANOPY FOUNDATION ARE PROVIDED BY THE GF GROUP STRUCTURAL ENGINEERS INC., BUT THERE WERE NO STRUCTURAL CALCULATIONS SUBMITTED FOR THE ACTUAL CANOPY. THOSE CALCULATIONS AND RELATED DRAWINGS REQUIRE PREPARATION BY A REGISTERED DESIGN PROFESSIONAL OF THE STATE OF ARIZONA PER THE IBC SECTION 107.1.
5. GENERAL: PLEASE PROVIDE FULL SIZE DRAWINGS (24" X 36") FOR THE NEW DRIVE UP CANOPY. DRAWINGS WILL INCLUDE PLANS, ELEVATIONS, DETAILS, NOTES, ETC. AS CURRENTLY SHOWN ON THE 8 1/2 X 11 SHEETS AND MUST BE SEALED BY A REGISTERED DESIGN PROFESSIONAL OF THE STATE OF ARIZONA. IN ADDITION TO SIGNING THE SEAL, THE REGISTRANT SHALL INCLUDE THE DATE THE DOCUMENT WAS SEALED AND THAT A NOTATION SHALL BE PLACED BENEATH THE SEAL (WRITTEN, TYPED, OR ELECTRONICALLY GENERATED) THAT PROVIDES THE DAY, MONTH, AND YEAR OF THE EXPIRATION OF THE CURRENT REGISTRATION (ARIZONA REVISED STATUTES 32-125, BOARD OF TECHNICAL REGISTRATION RULES R4-30-304).
6. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/04/2016 KROBLES1 OUT TO CUSTOMER Completed