Permit Number: T16CM02176
Parcel: 12310001H

Review Status: Active

Review Details: REVISION - - 3RD

Permit Number - T16CM02176
Review Name: REVISION - - 3RD
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
04/17/2017 MARTIN BROWN FIRE REVIEW Completed
04/17/2017 STANTEC PLUMBING-COMMERCIAL REVIEW Completed
04/17/2017 STANTEC ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. Why are the question mark symbols still shown under the light fixtures?
2. Sheet E3.1.1 - The lighting in the gift shop shown as critical braqnch circuit lighting does not meet the requirements of NEC 517.
3. Sheet E5.1.3 - Provide a panel and circuit for the receptacle shown with key note 4.
4. Sheet E5.1.3 - The med gas system should be on critical power see NEC 517.32 and NEC 517.33(A)(1). Please verify.
5. Sheet E7.0.2 - The gift shop lighting is not on normal power. The lighting plan shows critical power but it should be life safety per NEC 517.33. Please revise and correlate with the lighting plan.
04/17/2017 STANTEC BUILDING-COMMERCIAL REVIEW Reqs Change Per ICC/ANSI A117.1-2009 Sec. 405.2 a rail or other barrier must be provided under the stairs where the vertical clearance is less than 80-inches. A 2-inch high steel tube fastened horizontally to the floor is not a "barrier" and actually presents a trip hazard to someone not paying attention.
04/17/2017 STANTEC MECHANICAL-COMMERCIAL REVIEW Completed
11/16/2017 TWEIDEM1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Passed