Permit Review Detail
Review Status: Active
Review Details: REVISION - - 3RD
Permit Number - T16CM02176
Review Name: REVISION - - 3RD
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/17/2017 | MARTIN BROWN | FIRE | REVIEW | Completed | |
| 04/17/2017 | STANTEC | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 04/17/2017 | STANTEC | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Why are the question mark symbols still shown under the light fixtures? 2. Sheet E3.1.1 - The lighting in the gift shop shown as critical braqnch circuit lighting does not meet the requirements of NEC 517. 3. Sheet E5.1.3 - Provide a panel and circuit for the receptacle shown with key note 4. 4. Sheet E5.1.3 - The med gas system should be on critical power see NEC 517.32 and NEC 517.33(A)(1). Please verify. 5. Sheet E7.0.2 - The gift shop lighting is not on normal power. The lighting plan shows critical power but it should be life safety per NEC 517.33. Please revise and correlate with the lighting plan. |
| 04/17/2017 | STANTEC | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Per ICC/ANSI A117.1-2009 Sec. 405.2 a rail or other barrier must be provided under the stairs where the vertical clearance is less than 80-inches. A 2-inch high steel tube fastened horizontally to the floor is not a "barrier" and actually presents a trip hazard to someone not paying attention. |
| 04/17/2017 | STANTEC | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 11/16/2017 | TWEIDEM1 | TUCSON WATER NEW AREA DEVELOPMENT | REVIEW | Passed |