Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM02176
Parcel: 12310001H

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T16CM02176
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide an automatic faucet for the public lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03. [P0.0.1]
2. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012. [P0.0.1]
3. If the showers do not have pre-fabricated receptors, provide details to show that the construction of the receptors complies with the requirements of Section 417.5.2, IPC 2012. [P9.0.1]
4. Verify that the pipe sizes called out for the flush valves (WC-1, WC-2) will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for copper, PEX, or CPVC piping). At a minimum design flow rate of 25 GPM for a siphonic, flush-valve water closet, a 1" Type L copper pipe has a flow velocity of 9.7 FPS. Reference: Table 604.3, IPC 2012. [P9.0.1]
5. Revise the natural gas schematic to show the developed lengths of the piping from the regulators to the loads. Reference: Section 107.2.1, IBC 2012. [P7.0.4]
6. Verify the pressure of the natural gas entering the building: 2 PSI as shown on sheet P2.1.3 or 5 PSI as shown on sheet P7.0.4.
7. Verify the slope of the horizontal storm conductors. A 2% slope is identified only for one horizontal conductor located on the 1st level near column G.5-11.4; if the rest can be assumed to be at a 1% slope, some of the conductors may have to be re-sized. Reference: Table 1106.3, IPC 2012.
8. Verify that the storm drain conductors are not reduced in size in the direction of flow (e.g. see the conductor located near column L.5-11 - it starts at 8" level 9, changes to 6" from level 8 to level 6 and back to 8" on level 5. A similar change occurs at level 5 near F-11.) Reference: Section 1101.5, IPC 2012.
9. Clarify the labeling for the medical gas services shown on sheet MG2.1.3; use the piping system labels shown on sheet MG0.0.1 consistently (e.g. the gas delivered from the CO2 cylinders shouldn't change to nitrous oxide).
10. Use the pipe labels identified on sheet MG0.0.1 consistently.
11. Show the routes of the N2O, N2, and CO2 vents on the Medical Gas plans.
07/26/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.
2. Provide energy code compliance calculations for the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012.
3. Show that the proposed HVAC equipment meets the minimum efficiency requirements of Section C403.2.3, IECC 2012.
4. Show that the proposed Service water heating equipment meets the minimum efficiency requirements of Section C404.2, IECC 2012.
5. Show how one of the "Additional Efficiency Package Options" (C406, IECC 2012) is to be accomplished. Reference: Section C401.2, IECC 2012.
6. Provide notes on the drawings indicating what provisions have been made for commissioning the mechanical building systems per Section C408.2, IECC 2012.
7. The outside air schedule on sheet M0.0.1 indicates that 0.35 CFM/square foot of outside air will be supplied to the building. Provide calculations demonstrating that this will provide adequate ventilation using the current code. Reference: Section 403.2, IMC 2012.
8. Identify the required protection for duct and transfer openings in the fire-rated shafts. Reference: Section 107.2.1, IBC 2012.
07/27/2016 KEN BROUILLETTE FIRE REVIEW Passed
08/03/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change T16CM02176
BANNER NEW HOSPITAL & RENOVATION (BUILDING COMMENTS)
1. SHEETS G2.1 THROUGH G2.10: THESE SHEETS INDICATE FOR REFERENCE ONLY. WILL THE LIFE SAFETY ISSUES BE DESIGNATED IN THE 'FIT OUT' SUBMITTAL? PRELIMINARY COMMENTS WILL BE POSTED AT THIS TIME FOR THE BUILDING REVIEW.
2. SHEET G2.1; CODE REVIEW: THE RESIDENTIAL GROUP R-1 IS INDICATED AS AN OCCUPANCY CLASSIFICATION IN THIS PROJECT. WHAT EXACTLY IS THE USE IN THIS AREA (PER IBC SECTION 310.3)?
3. SHEET G2.1; CODE REVIEW: PER THE IBC SECTIONS 1009.3.1.2 AND 1022.2, THE STAIRWAY CONSTRUCTION IS REQUIRED TO BE 2 HOUR FIRE RESISTANT RATED FOR 4 LEVELS OR MORE, AND 1 HOUR FOR LESS THAN 4 LEVELS. THE DRAWINGS INDICATE 2 LEVELS AS THE CONTROL.
4. SHEET G2.1; CODE REVIEW: TABLE 1004.1.2 IN THE IBC CODE PROVIDES MAXIMUM FLOOR AREA ALLOWANCES FOR DIFFERENT OCCUPANCY FUNCTIONS. PLEASE VERIFY HOW THE ON-CALL ROOMS (200 GROSS SF/PERSON), LOCKER ROOMS (100 GROSS SF/PERSON), AND CHAPEL (7 NET SF/PERSON) WERE DERIVED.
5. SHEETS G2.1 AND G2.2; PLAN: PLEASE INDICATE THE FIRE RESISTANCE RATING FOR THE WEST WALL OF THE STAIR IN THE SOUTHWEST CORNER OF THE BUILDING.
6. SHEET G2.1; PLAN: PLEASE INDICATE THE FIRE RESISTANCE RATING FOR THE LOBBY WEST OF THE STAIR IN THE SOUTHWEST CORNER OF THE BUILDING.
7. SHEET G2.1; PLAN: PLEASE INDICATE THE FIRE RESISTANCE RATING FOR THE EXIT AREA NORTH OF THE STAIR IN THE SOUTHWEST CORNER OF THE BUILDING. IS THIS AN EXIT PASSAGEWAY?
8. SHEETS G2.1 AND G2.2; PLAN: PLEASE INDICATE THE FIRE RESISTANCE RATING FOR THE WEST WALL OF THE STAIR IN THE NORTHWEST CORNER OF THE BUILDING. IS THE INDICATED 1 HOUR FIRE BARRIER (IN BLUE) CORRECT AT THAT STAIR?
9. SHEETS G2.1 AND G2.2; PLAN: IT DOES NOT APPEAR ALL FIRE RESISTANCE RATED ELEMENTS ARE COMPLETE OR CORRECT ON THIS SHEET. PLEASE VERIFY AND IDENTIFY THOSE AREAS WITH THE APPROPRIATE FIRE RESISTANCE RATING DESIGNATION.
10. SHEETS G2.1 AND G2.2; DOOR SYMBOLS: THE DOOR FIRE RESISTANCE RATING WILL NOT BE REVIEWED UNTIL ALL RATED WALLS AND PARTITIONS ARE VERIFIED AND INDICATED.
11. SHEETS G2.1 AND G2.2; ACCESSIBILITY: THIS PROJECT ACCESSIBILITY WILL FOLLOW THE REQUIREMENTS OF THE 2012 IBC AND THE 2009 ICC/ANSI A117.1. PLEASE REVISE THE NOTE.
12. SHEETS G2.1 AND G2.2; PLAN: PLEASE COMPLETE THE EXIT ACCESS TRAVEL DISTANCES AND SMOKE COMPARTMENT BOUNDARIES ON THE PLAN.
13. SHEET G2.2; PLAN: THE SMOKE COMPARTMENT IN THE SOUTHWEST AREA OF THE BUILDING INDICATES 22,941 SF. THE IBC SECTION 407.5 LIMITS THE MAXIMUM AREA OF A SMOKE COMPARTMENT TO 22,500 SF. PLEASE VERIFY.
14. SHEET G2.2; PLAN: PLEASE VERIFY ON THE PLAN THE TRAVEL DISTANCE FROM A SMOKE COMPARTMENT IS 200 FEET MAXIMUM TO A SMOKE BARRIER DOOR PER THE IBC SECTION 407.5.
15. SHEET G2.2; PLAN: PLEASE INDICATE ON THE PLAN THE LOCATION OF ALL REFUGE AREAS IN EACH SMOKE COMPARTMENT PER THE IBC SECTION 407.5.1. INDICATE THE REQUIRED SF FOR EACH REFUGE AREA (SHOW AREA CALCULATION ON THE DRAWINGS), AND THE SF PROVIDED.
16. SHEET G2.2; PLAN: A DIMENSION IN A NORTH-SOUTH CORRIDOR IN THE LOWER PORTION OF THE BUILDING INDICATES A 1'-6" DIMENSION. PLEASE CLARIFY.
17. SHEET G2.2; PLAN: PER THE IBC SECTION 407.5, SMOKE BARRIERS (SECTION 709) ARE REQUIRED AT ALL SMOKE COMPARTMENT BOUNDARIES. PLEASE INDICATE ON THE DRAWINGS (GREEN DESIGNATION OR OTHER FIRE RESISTANT RATED WALL).
18. SHEETS G2.3 THROUGH G2.9: PLEASE REFERENCE COMMENTS FROM SHEETS G2.1 AND G2.2 FOR SIMILAR ISSUES ON THESE REFERENCE SHEETS.
19. SHEET G2.10; PLAN: COMPLETE OR CORRECT ALL FIRE RESISTANCE RATED ELEMENTS REQUIRED FOR THE ROOF.
20. SHEETS G3.1 THROUGH G3.8; U.L. ASSEMBLIES AND NOTES: PLEASE VERIFY ALL U.L. ASSEMBLIES NOTED ARE USED ON THESE DRAWINGS. PLEASE PROVIDE A TABLE ON THE DRAWINGS LISTING ALL FIRE RESISTANCE RATED WALLS AND PARTITIONS ON THIS PROJECT, AND RELATE A U.L. ASSEMBLY TO EACH.
21. SHEETS G3.1 THROUGH G3.8; U.L. ASSEMBLIES AND NOTES: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE FOLLOW THAT STANDARD.
22. SHEET AD2.1.0; REFLECTED CEILING PLAN DEMOLITION: PLEASE MOVE THE SECTION CUT AT GRIDS E AND 14.6 SO THE SECTION REFERENCE CAN BE READ.
23. SHEETS AD2.1.0 THROUGH AD2.1.1: PLEASE PROVIDE A NORTH ARROW ON THE PARTIAL PLANS.
24. SHEET AD2.1.1; PLANS 1 AND 3: THESE PLANS HAVE HEXAGONAL SYMBOLS WITH LETTERS AND NUMBERS IN THEM. WHAT DO THESE SYMBOLS REFERENCE?
25. SHEET AD2.2.0; SECTION 3: PLEASE MOVE THE SECTION CUT AT THE TOP OF THE WALL SECTION SO IT CAN BE READ.
26. SHEET AD2.2.0; SECTION 1: AT THE THIRD AND FOURTH LEVELS, AND IN BETWEEN THOSE LEVELS, THREE NOTES REFERENCE SHEET AD2.2.0. PLEASE REVISE THE SHEET NUMBER REFERENCE IN THOSE NOTES.
27. SHEET AD2.2.1; ELEVATION 1: A NOTE ON GRID F ABOVE THE FOURTH LEVEL REFERENCES DETAIL 3/A5.4.3. PLEASE REVISE THE REFERENCE.
28. SHEET A2.1.0; PLAN: A NOTE INDICATES A NEW AMBULANCE AND SHADE CANOPY. PLEASE CLARIFY ON THE DRAWING IF THIS PORTION IS UNDER A SEPARATE PERMIT, OR INCLUDED IN ONE OF THE PHASES OF THIS PROJECT.
29. SHEET A2.1.0; PLAN: STAIR 4 IN THE NORTHWEST AREA OF THE BUILDING INDICATES A 2 HOUR FIRE BARRIER (RED), A 1 HOUR FIRE BARRIER (BLUE), AND AN UNRATED EXTERIOR WALL. PLEASE VERIFY THE FIRE RESISTANCE RATINGS FOR THIS AREA.
30. SHEET A2.1.0; PLAN: THE IDF CLOSET (BELOW STAIR 4) INDICATES A 1 HOUR FIRE BARRIER (BLUE) AND AN UNRATED EXTERIOR WALL. PLEASE VERIFY THE FIRE RESISTANCE RATINGS FOR THIS AREA.
31. SHEET A2.1.0; PLAN: SHAFT #1 (BELOW STAIR 4) INDICATES A 2 HOUR FIRE BARRIER (RED), A 1 HOUR FIRE BARRIER (BLUE), AND AN UNRATED EXTERIOR WALL. PLEASE VERIFY THE FIRE RESISTANCE RATINGS FOR THIS AREA.
32. SHEET A2.1.0; PLAN: THE EMERGENCY ELECTRICAL RISER ROOM (ABOVE STAIR 3) INDICATES A 1 HOUR FIRE BARRIER (BLUE) AND AN UNRATED EXTERIOR WALL. PLEASE VERIFY THE FIRE RESISTANCE RATINGS FOR THIS AREA.
33. SHEET A2.1.0; PLAN: THE IDF CLOSET (ABOVE STAIR 3) IS NOT RATED AS THE CLOSET IN NOTE 30. PLEASE COORDINATE.
34. SHEET A2.1.0; PLAN: STAIR 3 IN THE SOUTHWEST AREA OF THE BUILDING INDICATES A 2 HOUR FIRE BARRIER (RED) AND AN UNRATED EXTERIOR WALL. PLEASE VERIFY THE FIRE RESISTANCE RATINGS FOR THIS AREA.
35. SHEET A2.1.0; PLAN: STAIR 2 IN THE SOUTH AREA OF THE BUILDING INDICATES A 2 HOUR FIRE BARRIER (RED), A 1 HOUR FIRE BARRIER (BLUE), AND AN UNRATED EXTERIOR WALL. PLEASE VERIFY THE FIRE RESISTANCE RATINGS FOR THIS AREA.
36. SHEET A2.1.0; PLAN: THE EXIT DOOR (EAST OF STAIR 2) DOES NOT INDICATE A RATED DOOR. PLEASE VERIFY.
37. SHEET A2.1.0; PLAN: THE ELEVATOR DOORS DO NOT INDICATE RATED DOORS. PLEASE VERIFY.
38. SHEET A2.1.0; PLAN: PLEASE VERIFY THE EXTERIOR WALLS (OTHER THAN THOSE AT SHAFTS AND ROOMS REQUIRING FIRE RESISTANCE RATED WALLS) MEET THE FIRE RESISTANCE RATING AS REQUIRED IN THE IBC TABLE 602.
39. SHEET A2.1.0; PLAN: PLEASE VERIFY THE ALLOWABLE AREA OF EXTERIOR WALL OPENINGS PER THE IBC TABLE 705.8 IS MET. INDICATE OPENING CALCULATIONS (ALLOWABLE AND ACTUAL) ON THE DRAWINGS AS REQUIRED.
40. SHEET A2.1.0; PLAN: PLEASE INDICATE ON THE DRAWINGS THE ELEVATOR(S) THAT MEET THE REQUIREMENTS OF THE IBC SECTION 3002.4 FOR AMBULANCE STRETCHER ACCOMMODATION.
41. SHEET A2.1.0; PLAN: PLEASE INDICATE ON THE DRAWINGS THE ELEVATORS THAT MEET THE REQUIREMENTS OF THE IBC SECTION 1007.2.1 FOR ACCESSIBLE MEANS OF EGRESS.
42. SHEETS A2.1.1 THROUGH A2.1.4: PLEASE VERIFY ALL FIRE RESISTANCE RATED WALLS AND PARTITIONS MATCH THOSE INDICATED ON SHEET A2.1.0. SEE COMMENTS 29 THROUGH 38.
43. SHEET A2.1.2; PLAN: PLEASE VERIFY THE 1 HOUR FIRE BARRIERS (BLUE) INDICATED BETWEEN THE IDF CLOSET AND THE ELECTRICAL ROOMS ARE REQUIRED IN THIS AREA. THEY ARE NOT SHOWN ON SHEET A2.1.0.
44. SHEET A2.1.2; PLAN: PLEASE VERIFY THE SMOKE PARTITIONS (ORANGE) INDICATED IN THE EXISTING CHILDREN'S MEDICAL CENTER ARE REQUIRED IN THIS AREA.
45. SHEET A2.1.3; PLAN: PLEASE VERIFY THE 1 HOUR FIRE BARRIERS (BLUE) INDICATED IN THE EVS EQUIPMENT STORAGE ROOM (NEAR GRIDS 10.7 AND 11) ARE REQUIRED IN THIS AREA. THEY ARE NOT SHOWN ON SHEET A2.1.0.
46. SHEET A2.2.0; PLAN: SEE COMMENTS 29 THROUGH 35, 37, AND 38.
47. SHEET A2.2.1; PLAN: PLEASE VERIFY THE 2 HOUR FIRE BARRIERS (RED) AND SMOKE PARTITIONS (ORANGE) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.2.0.
48. SHEETS A2.2.1 THROUGH A2.2.4: PLEASE VERIFY ALL FIRE RESISTANCE RATED WALLS AND PARTITIONS MATCH THOSE INDICATED ON SHEET A2.2.0. SEE COMMENTS 29 THROUGH 35, 37, AND 38.
49. SHEET A2.2.2; PLAN: PLEASE VERIFY THE 2 HOUR FIRE BARRIERS (RED) AND 1 HOUR SMOKE BARRIERS (GREEN) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.2.0.
50. SHEET A2.2.3; PLAN: PLEASE VERIFY THE 2 HOUR FIRE BARRIERS (RED), 1 HOUR FIRE BARRIERS (BLUE), AND 1 HOUR SMOKE BARRIERS (GREEN) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.2.0.
51. SHEET A2.2.4; PLAN: PLEASE VERIFY THE 1 HOUR FIRE BARRIERS (BLUE) AND 1 HOUR SMOKE BARRIERS (GREEN) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.2.0.
52. SHEET A2.3.0; PLAN: SEE COMMENTS 29 THROUGH 35, 37, AND 38.
53. SHEET A2.3.1; PLAN: PLEASE VERIFY THE 2 HOUR FIRE BARRIERS (RED), 1 HOUR FIRE BARRIERS (BLUE), 1 HOUR SMOKE BARRIERS (GREEN), AND SMOKE PARTITIONS (ORANGE) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.3.0.
54. SHEETS A2.3.1 THROUGH A2.3.4: PLEASE VERIFY ALL FIRE RESISTANCE RATED WALLS AND PARTITIONS MATCH THOSE INDICATED ON SHEET A2.3.0. SEE COMMENTS 29 THROUGH 35, 37, AND 38.
55. SHEET A2.3.2; PLAN: PLEASE VERIFY THE 2 HOUR FIRE BARRIERS (RED), 1 HOUR FIRE BARRIERS (BLUE), 1 HOUR SMOKE BARRIERS (GREEN), AND SMOKE PARTITIONS (ORANGE) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A.2.3.0.
56. SHEET A2.3.3; PLAN: PLEASE VERIFY THE 1 HOUR FIRE BARRIERS (BLUE), 1 HOUR SMOKE BARRIERS (GREEN), AND SMOKE PARTITIONS (ORANGE) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.3.0.
57. SHEET A2.3.4; PLAN: PLEASE VERIFY THE 1 HOUR FIRE BARRIERS (BLUE), 1 HOUR SMOKE BARRIERS (GREEN), AND SMOKE PARTITIONS (ORANGE) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.3.0.
58. SHEET A2.4.0; PLAN: SEE COMMENTS 29 THROUGH 35, 37, AND 38.
59. SHEET A2.4.1; PLAN: PLEASE VERIFY THE 1 HOUR FIRE BARRIERS (BLUE) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.4.0.
60. SHEETS A2.4.1 THROUGH A2.4.4: PLEASE VERIFY ALL FIRE RESISTANCE RATED WALLS AND PARTITIONS MATCH THOSE INDICATED ON SHEET A2.4.0. SEE COMMENTS 29 THROUGH 35, 37, AND 38.
61. SHEETS A2.4.1 AND A2.4.1d; PLAN: WHY ARE THESE PLANS COULDED IN TWO LOCATIONS? PLEASE CLARIFY.
62. SHEET AS.4.2; PLAN: PLEASE VERIFY THE 2 HOUR FIRE BARRIERS (RED), THE 1 HOUR FIRE BARRIERS (BLUE), THE 1 HOUR SMOKE BARRIERS (GREEN) AND THE SMOKE PARTITIONS (ORANGE) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.4.0.
63. SHEET A2.4.3; PLAN: PLEASE VERIFY THE 1 HOUR FIRE BARRIERS (BLUE) AND THE SMOKE PARTITIONS (ORANGE) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.4.0.
64. SHEET A2.5.0; PLAN: SEE COMMENTS 29 THROUGH 32, 35, 37, AND 38.
65. SHEET A2.5.1; PLAN: PLEASE VERIFY THE 1 HOUR FIRE BARRIERS (BLUE), THE 1 HOUR SMOKE BARRIERS (GREEN), AND THE SMOKE PARTITIONS (ORANGE) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.5.0.
66. SHEETS A2.5.1 THROUGH A2.5.4: PLEASE VERIFY ALL FIRE RESISTANCE RATED WALLS AND PARTITIONS MATCH THOSE INDICATED ON SHEET A2.5.0. SEE COMMENTS 29 THROUGH 32, 35, 37, AND 38.


67. SHEET A2.5.2; PLAN: PLEASE VERIFY THE 1 HOUR FIRE BARRIERS (BLUE), THE 1 HOUR FIRE PARTITIONS (TURQUOISE), THE 1 HOUR SMOKE BARRIERS (GREEN), AND THE SMOKE PARTITIONS (ORANGE) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.5.0.
68. SHEET A2.5.3; PLAN: PLEASE VERIFY THE 1 HOUR FIRE BARRIERS (BLUE), THE 1 HOUR SMOKE BARRIERS (GREEN), AND THE SMOKE PARTITIONS (ORANGE) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.5.0.
69. SHEET A2.5.4; PLAN: PLEASE COMPLETE THE FIRE RESISTANCE RATED WALLS AND PARTITIONS ON THIS PLAN.
70. SHEET A2.6.0; PLAN: SEE COMMENTS 29 THROUGH 31, 35, 37, AND 38.
71. SHEET A2.6.5; PLAN: PLEASE VERIFY THE 1 HOUR FIRE BARRIERS (BLUE), THE 1 HOUR SMOKE BARRIERS (GREEN), AND THE SMOKE PARTITIONS (ORANGE) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.6.0.
72. SHEETS A2.6.5 THROUGH A2.6.7: PLEASE VERIFY ALL FIRE RESISTANCE RATED WALLS AND PARTITIONS MATCH THOSE INDICATED ON SHEET A2.6.0. SEE COMMENTS 29 THROUGH 31, 35, 37, AND 38.
73. SHEET A2.6.6; PLAN: PLEASE VERIFY THE 1 HOUR FIRE BARRIERS (BLUE), THE 1 HOUR FIRE PARTITIONS (TURQUOISE), THE 1 HOUR SMOKE BARRIERS (GREEN), AND THE SMOKE PARTITIONS (ORANGE) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.6.0.
74. SHEET A2.6.7; PLAN: PLEASE VERIFY THE 1 HOUR FIRE BARRIERS (BLUE), THE 1 HOUR SMOKE BARRIERS (GREEN), AND THE SMOKE PARTITIONS (ORANGE) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.6.0.
75. SHEET A2.7.0; PLAN: SEE COMMENTS 29 THROUGH 31, 35, 37, AND 38.
76. SHEET A2.7.5; PLAN: PLEASE VERIFY THE 1 HOUR FIRE BARRIERS (BLUE) AND THE SMOKE PARTITIONS (ORANGE) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.7.0.
77. SHEETS A2.7.5 THROUGH A2.7.7: PLEASE VERIFY ALL FIRE RESISTANCE RATED WALLS AND PARTITIONS MATCH THOSE INDICATED ON SHEET A2.7.0. SEE COMMENTS 29 THROUGH 31, 35, 37, AND 38.
78. SHEET A2.7.6; PLAN: PLEASE VERIFY THE 1 HOUR FIRE BARRIERS (BLUE), THE 1 HOUR FIRE PARTITIONS (TURQUOISE), THE 1 HOUR SMOKE BARRIERS (GREEN), AND THE SMOKE PARTITIONS (ORANGE) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.7.0.
79. SHEET A2.7.7; PLAN: PLEASE VERIFY THE 1 HOUR FIRE BARRIERS (BLUE), THE 1 HOUR SMOKE BARRIERS (GREEN), AND THE SMOKE PARTITIONS (ORANGE) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.7.0.
80. SHEET A2.8.0; PLAN: SEE COMMENTS 29 THROUGH 31, 35, 37, AND 38.
81. SHEET A2.8.5; PLAN: PLEASE VERIFY THE 1 HOUR FIRE BARRIERS (BLUE) AND THE SMOKE PARTITIONS (ORANGE) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.8.0.
82. SHEETS A2.8.5 THROUGH A2.8.7: PLEASE VERIFY ALL FIRE RESISTANCE RATED WALLS AND PARTITIONS MATCH THOSE INDICATED ON SHEET A2.8.0. SEE COMMENTS 29 THROUGH 31, 35, 37, AND 38.
83. SHEET A2.8.6; PLAN: PLEASE VERIFY THE 1 HOUR FIRE BARRIERS (BLUE), THE 1 HOUR FIRE PARTITIONS (TURQUOISE), THE 1 HOUR SMOKE BARRIERS (GREEN), AND THE SMOKE PARTITIONS (ORANGE) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.8.0.
84. SHEET A2.8.7; PLAN: PLEASE VERIFY THE 1 HOUR FIRE BARRIERS (BLUE), THE 1 HOUR SMOKE BARRIERS (GREEN), AND THE SMOKE PARTITIONS (ORANGE) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.8.0.
85. SHEET A2.9.0; PLAN: SEE COMMENTS 29 THROUGH 31, 35, 37, AND 38.
86. SHEET AS.9.5; PLAN: PLEASE VERIFY THE 1 HOUR FIRE BARRIERS (BLUE) AND THE SMOKE PARTITIONS (ORANGE) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.9.0.
87. SHEETS A2.9.5 THROUGH A2.9.7: PLEASE VERIFY ALL FIRE RESISTANCE RATED WALLS AND PARTITIONS MATCH THOSE INDICATED ON SHEET A2.9.0. SEE COMMENTS 29 THROUGH 31, 35, 37, AND 38.
88. SHEET A2.9.6; PLAN: PLEASE VERIFY THE 2 HOUR FIRE BARRIERS (RED), THE 1 HOUR FIRE BARRIERS (BLUE), THE 1 HOUR FIRE PARTITIONS (TURQUOISE), THE 1 HOUR SMOKE BARRIERS (GREEN), AND THE SMOKE PARTITIONS (ORANGE) INDICATED IN SEVERAL LOCATIONS ARE REQUIRED. THEY ARE NOT SHOWN ON SHEET A2.9.0.
89. SHEET A2.10.6; ROOF LEVEL PLAN: PLEASE VERIFY ALL FIRE RESISTANCE RATED WALLS ARE INDICATED ON THE PLAN.
90. SHEET A2.10.7; ROOF LEVEL PLAN: PLEASE VERIFY ALL FIRE RESISTANCE RATED WALLS ARE INDICATED ON THE PLAN.
91. SHEETS A3.1.0 THROUGH A3.4.0; REFLECTED CEILING PLAN: PLEASE VERIFY ALL FIRE RESISTANCE RATED WALLS ARE INDICATED ON THESE PLANS.
92. SHEET A6.1.1; STAIR PLANS: PLEASE VERIFY THE FIRE RESISTANCE RATED WALLS MATCH THOSE SHOWN AT STAIR #1 ON THE A2 SHEETS.
93. SHEET A6.1.2; STAIR PLANS: PLEASE VERIFY THE FIRE RESISTANCE RATED WALLS MATCH THOSE SHOWN AT STAIR #2 ON THE A2 SHEETS. VERIFY THE EXTERIOR WALL RATING.
94. SHEET A6.1.3; STAIR PLANS: PLEASE VERIFY THE FIRE RESISTANCE RATED WALLS MATCH THOSE SHOWN AT STAIR #3 ON THE A2 SHEETS. VERIFY THE EXTERIOR WALL RATING, AND REVISE THE FIFTH LEVEL PLAN.
95. SHEET A6.1.4; STAIR PLANS: PLEASE VERIFY THE FIRE RESISTANCE RATED WALLS MATCH THOSE SHOWN AT STAIR #4 ON THE A2 SHEETS. VERIFY THE EXTERIOR WALL RATING.
96. SHEET A6.1.5; STAIR PLAN: PLEASE VERIFY THE FIRE RESISTANCE RATED WALLS MATCH THOSE SHOWN AT STAIR #4 ON THE A2 SHEETS. VERIFY THE EXTERIOR WALL RATING.
97. SHEET A6.2.1; ELEVATOR PLANS: PLEASE VERIFY THE FIRE RESISTANCE RATED WALLS MATCH THOSE SHOWN AT THE ELEVATORS ON THE A2 SHEETS.
98. SHEET A6.2.2; ELEVATOR PLANS: PLEASE VERIFY THE FIRE RESISTANCE RATED WALLS MATCH THOSE SHOWN AT THE ELEVATORS ON THE A2 SHEETS.
99. SHEET A9.3.1; DOOR SCHEDULES: ARE THE DOOR TYPES, AS LISTED IN THE SCHEDULES, SHOWN IN THE SPECIFICATIONS?
08/05/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change BANNER UNIVERSITY MEDICAL CENTER TUCSON EXPANSION.
JOB # 14-0888.0
PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS. ALSO PROVIDE A WRITTEN RESPONSE.
#1. PLAN SHEET E1.4.10 IS NOT LISTED ON THE PLAN SHEET INVENTORY 'G0.2'.
#2. (A). REF: PLAN SHEET E7.0.1, NOTE ON THE TRANSFORMER GROUNDING DETAIL REFERS TO PLAN SHEET E7.00 FOR THE BONDING JUMPER SIZE. COULD NOT LOCATE PLAN SHEET E7.00.
(B). REF: PLAN SHEET E7.0.2, KEYNOTE #3 AND #4, REFERS TO PLAN SHEET E8.0.1. COULD NOT LOCATE PLAN SHEET E8.0.1.
#3. REF: PLAN SHEET E8.4.0, ENLARGED ELECTRIC ROOM DETAILS #1 AND #2 SHOW EGRESS DOOR SWING INWARD AT COLUMNS N-7 (NORMAL ELECTRIC ROOM). AND THE UPS ROOM. THIS WOULD BE IN VIOLATION OF NEC ART. 110.26C2.
#4. PLEASE SUBMIT A SELECTIVE COORDINATION ANALYSIS FOR THE CIRCUIT PATHS REQUIRED TO BE SELECTIVELY COORDINATED PER NEC ARTICLES 517,620, 700, 701, 708. PROVIDE A STATEMENT CLEARLY STATING THAT SELECTIVE COORDINATION HAS BEEN ACHIEVED, AND APPROVED BY THE ENGINEER OF RECORD, PRIOR TO FINALIZATION OF THIS PROJECT.
#5. ARE THE ENG.GEN-1,2,3,4, AND ASSOCIATED EQUIPMENT SHOWN ON PLAN SHEET E1.4.10 NEW FOR THIS PHASE OF CONST? IF YES, PLEASE SHOW THE LOCATION ON THE PLANS.
REF: 2012 IBC SEC. 107.2.1, 2011 NEC
08/09/2016 CLAYTON TREVILLYAN ADA REVIEW Passed N/A. ADA review will occur on next submittal.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/26/2016 BGRANT1 APPROVAL SHELF Completed
08/26/2016 BGRANT1 OUT TO CUSTOMER Completed
08/26/2016 BGRANT1 REJECT SHELF Completed