Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T16CM02176
Parcel: 12310001H

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T16CM02176
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/06/2016 MARTIN BROWN FIRE REVIEW Passed FIRE DOES NOT NEED TO REVIEW THE SUB-STRUCTURE.-KENB
04/13/2016 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: Banner University Medical Center - Steel and Stairs Package
T16CM02176
Building Plan (1st Review)

TRANSMITTAL DATE: April 13, 2016

1. The steel and stairs package has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The steel and stairs package has been reviewed and it appears that the plans match development package DP16-0027. But until development package DP16-0027 is approved Zoning cannot approve the steel and stairs package.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
04/14/2016 LOREN MAKUS ENGINEERING REVIEW Approved
04/26/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEETS S2.2.3 BP2, S2.3.3 BP2, S2.4.3 BP2, S2.5.3 BP2, S2.6.7 BP2, S2.7.7 BP2, S2.8.7 BP2, S2.9.7 BP2, AND S2.10.7 BP2: THE ELEVATION REFERENCE FOR THE FRAME ON GRID N, BETWEEN GRIDS 10 TO 13, IS IDENTIFIED AS 1/S3.2.4. PLEASE REVISE THE REFERENCE NUMBER.
2. SHEET S2.11.6 BP2; FRAMING PLAN 2: PLEASE PROVIDE THE MACHINE BEAMS (BY OTHERS) CALCULATIONS AND INDICATE THE BEAM SIZES ON THE PLAN.
3. GENERAL: SHOULD A NOTE BE ADDED TO THE SHEETS FOR A MOMENT CONNECTION OF A BEAM TO A BEAM AS INDICATED ON SHEETS S2.2.0 BP2 THROUGH S2.10.7 BP2? PLEASE VERIFY, AND ADD A DETAIL REFERENCE TO THOSE SHEETS.
4. SHEETS S2.14.1 BP2 THROUGH S2.14.3 BP2: IS THIS PART OF THE STRUCTURAL STEEL/STAIRS PACKAGE? PLEASE VERIFY.
5. SHEET S2.14.1 BP2; GENERAL STRUCTURAL NOTES: THE MATERIALS OF CONSTRUCTION DO NOT INCLUDE STRUCTURAL MASONRY (INDICATED ON SHEET S2.14.3 BP2), AND NO SPECIAL INSPECTIONS ARE DESIGNATED FOR MASONRY. PLEASE VERIFY.
6. SHEETS S2.14.1 BP2 THROUGH S2.14.3 BP2: WERE CALCULATIONS SUBMITTED FOR THE TEP VAULT AND FOUNDATION? PLEASE VERIFY.
7. GENERAL: IT WILL BE ASSUMED THAT THE FLOOR LOADINGS INDICATED ON SHEETS S1.1.0 BP2 THROUGH S1.13.0 BP2 HAVE NOT BEEN REVISED SINCE THE FOUNDATION REVIEW (T16CM00577) WAS COMPLETED AND APPROVED. PLEASE VERIFY.
8. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/31/2016 RBENT1 OUT TO CUSTOMER Completed