Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T15CM07660
Parcel: 134234120

Address:
203 S WILMOT RD

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T15CM07660
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/14/2016 KROBLES1 OUT TO CUSTOMER Completed