Permit Number: T15CM07660
Parcel: 134234120

Address:
203 S WILMOT RD

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T15CM07660
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Show that the proposed water booster pump system includes a low pressure cutoff. Reference: Section 606.5.5, IPC 2012.
02/22/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide power for the new booster pump 'BP1' on the electrical plans. Per plumbing revision.
Ref: IBC 107.2.1, 2011 NEC.
02/22/2016 ROBERT SHERRY WATER REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/25/2016 EGALLET1 OUT TO CUSTOMER Completed