Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T15CM07660
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/22/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Show that the proposed water booster pump system includes a low pressure cutoff. Reference: Section 606.5.5, IPC 2012. |
02/22/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide power for the new booster pump 'BP1' on the electrical plans. Per plumbing revision. Ref: IBC 107.2.1, 2011 NEC. |
02/22/2016 | ROBERT SHERRY | WATER | REVIEW | Completed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/25/2016 | EGALLET1 | OUT TO CUSTOMER | Completed |