Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM02190
Parcel: 14041134D

Review Status: Completed

Review Details: REVISION - - 4TH

Permit Number - T15CM02190
Review Name: REVISION - - 4TH
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2016 KEN BROUILLETTE FIRE REVIEW Approved
03/10/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
03/10/2016 ROBERT SHERRY WATER REVIEW Completed
03/10/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Condensate drains shall be terminated at an approved disposal location; revise details 1/M0.3 and 7/M0.3 to agree with the condensate drains shown on sheets M2.1 through M2.7. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
03/23/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Please provide a written response.
#1. The electrical brief narrative provided with the construction documents for all the electrical revisions did not contain enough detailed information to provide a complete plan review. Also the keynote information was not provided on all the plan sheets. Some of the letters in the deltas did not seem to apply to the clouded in areas. Example, plan sheet E3.3 has a K delta by the restrooms which refers to the "NEW THIRD SERVICE" ?
#2.Please identify the generators shown on the floor plans.
#3. It was noticed that full compliance with the Outdoor Lighting Code was not demonstrated as required per section 104 and 401 such as Lumen calc's and shielding requirements.
Ref: IBC sec. 107.2.1
03/25/2016 LOREN MAKUS ENGINEERING REVIEW Approved
04/01/2016 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: HomeGoods Distribution Center
T15CM02190
Building Plan (1st Review)

TRANSMITTAL DATE: April 1, 2016

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning has no issue with the proposed reversion but will not approve the plans until all PDSD agencies have approved the plan.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
04/05/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. GENERAL: NEW SHEETS S8.1 AND S8.2 HAVE BEEN ADDED AND ARE NOT INDICATED ON THE LATEST SHEET INDEX (SHEET A0.1). PLEASE ADD.
2. GENERAL: PLEASE INCLUDE IN THE SUMMARY LETTER OF THE CHANGES TO THE DRAWINGS THE SHEET NUMBERS THAT THESE CHANGES AFFECTED. THIS REVIEW WAS ORIGINALLY FOR DELTA M, BUT SINCE IT WAS SUBMITTED, DELTA N AND DELTA P REVISIONS HAVE BEEN ADDED. PLEASE CLOUD ALL CHANGES ON THE DRAWINGS.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/29/2016 KROBLES1 OUT TO CUSTOMER Completed