Permit Number: T15CM02190
Parcel: 14041134D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15CM02190
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2015 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Reqs Change Sheet S1.0
1) Please coordinate the F4 footing between the plan schedule and the calculations per IBC Section 107.2.1. The calculations for the FF1 footing on sheet #61 calls for 6-#6 bars each way, but the plan schedule for the F4 footing only calls for 5-#6 bars.

Sheets A6.2 and E2.8
2) Please provide an exiting plan for the office area and coordinate the associated exit and egress illumination with emergency power in accordance with the requirements of IBC Chapter 10. The exit signage shown on sheet E2.8 directs occupants back into the warehouse area and doesn't provide sufficient exit signage in the supervisor's area to two separate exits. In order to verify the required egress widths, the proper means of egress and the appropriate exit signage, an exit plan is necessary. It would be beneficial to provide it in the plan submittal, but it is not necessary. However, the information does need to be coordinated throughout the plan submittal.
06/03/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/03/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed