Permit Number: T15CM02190
Parcel: 14041134D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15CM02190
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/01/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide the supporting NFRC fenestration product ratings for the U-factor and the SHGC values for the proposed fenestration as described in footnote (b) of the Envelope Compliance Certificate. [Initial comment: Provide NFRC fenestration product ratings for the U-factor and the SHGC values for the energy code compliance calculations (e.g. COMcheck) or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Reference: Section C303.1.3, IECC 2012.]
06/01/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Initial comment: Provide structural calculations to show that the proposed overflow scuppers are adequate to protect the roof from the rain load. Reference: Sections 1101, 1106 and 1108, IPC 2012, and Sections 1611.1 and 1611.3, IBC 2012.]
2. Revise water pressure calculations. [Second comment: Provide the civil RPBP specifications.] [Initial comment: Provide listing information for the proposed reduced pressure backflow preventer that shows that the pressure drop for the assembly is only 8 PSI. Reference: Section 604.1, IPC 2012.]
06/03/2015 AROMERO4 BUILDING-COMMERCIAL REVIEW Needs Review