Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T15CM02190
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/01/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
06/01/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide the supporting NFRC fenestration product ratings for the U-factor and the SHGC values for the proposed fenestration as described in footnote (b) of the Envelope Compliance Certificate. [Initial comment: Provide NFRC fenestration product ratings for the U-factor and the SHGC values for the energy code compliance calculations (e.g. COMcheck) or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Reference: Section C303.1.3, IECC 2012.] |
06/01/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not addressed. [Initial comment: Provide structural calculations to show that the proposed overflow scuppers are adequate to protect the roof from the rain load. Reference: Sections 1101, 1106 and 1108, IPC 2012, and Sections 1611.1 and 1611.3, IBC 2012.] 2. Revise water pressure calculations. [Second comment: Provide the civil RPBP specifications.] [Initial comment: Provide listing information for the proposed reduced pressure backflow preventer that shows that the pressure drop for the assembly is only 8 PSI. Reference: Section 604.1, IPC 2012.] |
06/03/2015 | AROMERO4 | BUILDING-COMMERCIAL | REVIEW | Needs Review |