| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/06/2013 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 08/06/2013 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 09/04/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/04/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide an exhaust fan for the restroom. The fan shall run whenever the A/C unit is delivering air to the restroom. |
| 09/04/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide cleanouts sized for the nominal pipe size. 2. Provide a temperature mixing valve for the lavatory listed to ASSE 1070. 3. Provide a shower valve listed to ASSE 1016. 4. The maximum water flow for the lavatory is 0.50 GPM. |
| 09/04/2013 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 09/06/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/06/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/09/2013 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 09/09/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approv-Cond | PROVIDE ADDRESSING AND FIRE EXTINGUISHER |