Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM07582
Parcel: 14043013B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07582
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
11/30/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/30/2012 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/30/2012 ROBERT SHERRY WATER REVIEW Approved
11/30/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/30/2012 LAITH ALSHAMI ENGINEERING REVIEW Approved
11/30/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/30/2012 MARTIN BROWN FIRE REVIEW Approved
11/30/2012 RONALD BROWN ADA REVIEW Passed
12/21/2012 GERRY KOZIOL WWM REVIEW Passed
12/21/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved