Permit Number: T12CM03807
Parcel: 125110580

Address:
3825 E 2ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM03807
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/02/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the termination point for the temperature and pressure relief valve for the water heater; detail 203 refers to the drawing but nothing is shown there. Reference: Section 103.2.3 and 608.5, UPC 2006.
2. Provide protection of the trap seals for all floor drains subject to infrequent use. Pro-vent Trap Guards are not approved for use in the City of Tucson. Reference: Sections 316.4, 1007.0, and 1007.1, UPC 2006, as amended by the City of Tucson.
07/02/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/02/2012 ROBERT SHERRY WATER REVIEW Denied Tucson Water limits a 1" meter to a maximum demand of 25 GPM. Your calculations indicate a demand of 31 GPM; provide a letter from Tucson Water confirming that the use of a 1" water meter will be allowed for this project.
07/09/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM03807
3825 E 2nd ST
TI School

1. Sheet E4.0, the fault current given is for the new 1200 A
CT enclosure and the new main disconnects and panels for Y and Z. The fault current calculation fails to mention the existing electrical equipment which may see a different and higher fault current, please address the fault current situation to the existing equipment.
2. The 2 parallel sets of 4#500 mcm AL under the 2005 NEC 310.16 show approved for 620 amps under the 75 degree C
table, the connected load shown is 1014 amps and the demand load is 797 amps ?

Ray T Majuta
Elect Plan Review
PDSD, City of Tucson
7/09/2012