Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM03807
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/02/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the termination point for the temperature and pressure relief valve for the water heater; detail 203 refers to the drawing but nothing is shown there. Reference: Section 103.2.3 and 608.5, UPC 2006. 2. Provide protection of the trap seals for all floor drains subject to infrequent use. Pro-vent Trap Guards are not approved for use in the City of Tucson. Reference: Sections 316.4, 1007.0, and 1007.1, UPC 2006, as amended by the City of Tucson. |
| 07/02/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/02/2012 | ROBERT SHERRY | WATER | REVIEW | Denied | Tucson Water limits a 1" meter to a maximum demand of 25 GPM. Your calculations indicate a demand of 31 GPM; provide a letter from Tucson Water confirming that the use of a 1" water meter will be allowed for this project. |
| 07/09/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM03807 3825 E 2nd ST TI School 1. Sheet E4.0, the fault current given is for the new 1200 A CT enclosure and the new main disconnects and panels for Y and Z. The fault current calculation fails to mention the existing electrical equipment which may see a different and higher fault current, please address the fault current situation to the existing equipment. 2. The 2 parallel sets of 4#500 mcm AL under the 2005 NEC 310.16 show approved for 620 amps under the 75 degree C table, the connected load shown is 1014 amps and the demand load is 797 amps ? Ray T Majuta Elect Plan Review PDSD, City of Tucson 7/09/2012 Ray.Majuta@tucsonaz.gov |