Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM00605
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/26/2011 | MARTIN BROWN | FIRE | REVIEW | Denied | Fire Comments: The fire wall for the property line must continue through the overhang on the easr side. See IFC Chapter 7 and IBC 705. |
| 04/26/2011 | MARTIN BROWN | FIRE | REVIEW | Denied | The plans have a new note but still show a mixture of steel and wood framing and no type x gyp board. |
| 05/06/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | In order to properly review the three connected structures for code compliance pertaining ro fire separations and overhangs (reference Fire comments), please provide a site plan showing all connected properties and their physical relationship to each other and site parking and drive entrances and property lines. |
| 05/06/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. Fixture type F1A is a recessed type installed in a portal, please discribe the installation. 2. Provide to what source receptacles for signs are to be connected, and which circuits to be used. Ray Majuta PDSD, City of Tuc Elect Pln Ck 5/6/11 |
| 05/17/2011 | CPIERCE1 | ZONING | REVIEW | Needs Review |