Permit Number: T10CM01426
Parcel: 129041810

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T10CM01426
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project:T10CM01426
2012 E Broadway, Photo Voltaic Installation,
69 panels
Electrical plans denied for following:

.
1. Electrical Plans to be sealed by an Electrical Engineer.
2. Plans show an increase of service from 200 amp to 400 amp, The increase in conductors,over-current protection, conduits, and grounding for the new service must be shown on one line diagram. Also a fault current analysis of the fault current on thur to the panels must be provided.
3. Specify under Special notes, Installation to comply per 2005 NEC.
4. The "CONT. #10 EQG" is incorrect, this conductor is a
Grounding Electrode Conductor and must be sized per
2005 NEC 690-47.C. Both AC and DC GEC to be sized per 690-47.C
5. Provide location on floor plan or sheet A1.0 of AC disconnects , inverters and combiner panel.


Ray T Majuta
PDSD, City of Tuc,
Elect Plan Ck,
6/22/10
Ray>Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
06/24/2010 CPIERCE1 OUT TO CUSTOMER Completed
06/24/2010 SUE REEVES REJECT SHELF Completed