Permit Number - T10CM01426
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/22/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project:T10CM01426 2012 E Broadway, Photo Voltaic Installation, 69 panels Electrical plans denied for following: . 1. Electrical Plans to be sealed by an Electrical Engineer. 2. Plans show an increase of service from 200 amp to 400 amp, The increase in conductors,over-current protection, conduits, and grounding for the new service must be shown on one line diagram. Also a fault current analysis of the fault current on thur to the panels must be provided. 3. Specify under Special notes, Installation to comply per 2005 NEC. 4. The "CONT. #10 EQG" is incorrect, this conductor is a Grounding Electrode Conductor and must be sized per 2005 NEC 690-47.C. Both AC and DC GEC to be sized per 690-47.C 5. Provide location on floor plan or sheet A1.0 of AC disconnects , inverters and combiner panel. Ray T Majuta PDSD, City of Tuc, Elect Plan Ck, 6/22/10 Ray>Majuta@tucsonaz.gov |