Permit Number: T09CM02372
Parcel: 21116006A

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T09CM02372
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2009 DAVE MANN FIRE REVIEW Approved
09/09/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: DEFERRED SUBMITTALS MUST BE APPROVED BY LEERAY HANLY BEFORE PLANS CAN BE APPROVED.
2. GENERAL: TWO SETS OF CALCULATIONS MUST BE SUBMITTED BEFORE PLANS CAN BE APPROVED.
3. SHEET 15 OF 26 (DETAILS 5 AND 6); CALCULATIONS PAGE 19: THE CALCULATIONS INDICATE THE TOP PLATE ON THE MASONRY WALL IS TO BE ANCHORED TO THE WALL WITH 5/8" DIAMETER ANCHORS AT 24" OC, WHILE DETAILS 5 AND 6 INDICATE 1/2" DIAMETER ANCHORS AT 32" OC. CLARIFY. DETAILS 8 AND 10 AGREE WITH THE CALCULATIONS.
09/10/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/18/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Passed
09/18/2009 RMYERS1 WWM REVIEW Passed 1. No wastewater connected fixtures.
09/18/2009 RMYERS1 WATER REVIEW Passed
09/21/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/23/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 12635 W Mile Wide Rd
T09CM02372
City of Tucson Water, Booster Station

The Electrical Plans have been denied for the following:
1. The 2005 NEC Sec 230-95 requires Ground Fault Protection of Service Equipment. This protection shall be provided for services 150 volts to ground or more, for each service disconnect rated 1000 amps or more. NEC 250-95 c, requires a written record of the test available to our department prior to energizing. Please provide this information on the one line diagram.
2. Please note also on one line diagram "Label Services
"SERVICE MCC-3 ONE OF TWO", and "SERVICE MCC-4 TWO OF TWO" .
3. Please clarify, under the disconnects for each Booster Pump, you show a 3-phase system feeding the pump however noted is a 2-phase actually feeding the pump?


Ray T Majuta
PSDS City of Tucson
Elect Plan Ck
9/27/09
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
10/08/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
10/08/2009 DELMA ROBEY REJECT SHELF Completed