Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T09CM02372
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/08/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 09/09/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. GENERAL: DEFERRED SUBMITTALS MUST BE APPROVED BY LEERAY HANLY BEFORE PLANS CAN BE APPROVED. 2. GENERAL: TWO SETS OF CALCULATIONS MUST BE SUBMITTED BEFORE PLANS CAN BE APPROVED. 3. SHEET 15 OF 26 (DETAILS 5 AND 6); CALCULATIONS PAGE 19: THE CALCULATIONS INDICATE THE TOP PLATE ON THE MASONRY WALL IS TO BE ANCHORED TO THE WALL WITH 5/8" DIAMETER ANCHORS AT 24" OC, WHILE DETAILS 5 AND 6 INDICATE 1/2" DIAMETER ANCHORS AT 32" OC. CLARIFY. DETAILS 8 AND 10 AGREE WITH THE CALCULATIONS. |
| 09/10/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/18/2009 | RICK MYERS | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 09/18/2009 | RMYERS1 | WWM | REVIEW | Passed | 1. No wastewater connected fixtures. |
| 09/18/2009 | RMYERS1 | WATER | REVIEW | Passed | |
| 09/21/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 09/23/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: 12635 W Mile Wide Rd T09CM02372 City of Tucson Water, Booster Station The Electrical Plans have been denied for the following: 1. The 2005 NEC Sec 230-95 requires Ground Fault Protection of Service Equipment. This protection shall be provided for services 150 volts to ground or more, for each service disconnect rated 1000 amps or more. NEC 250-95 c, requires a written record of the test available to our department prior to energizing. Please provide this information on the one line diagram. 2. Please note also on one line diagram "Label Services "SERVICE MCC-3 ONE OF TWO", and "SERVICE MCC-4 TWO OF TWO" . 3. Please clarify, under the disconnects for each Booster Pump, you show a 3-phase system feeding the pump however noted is a 2-phase actually feeding the pump? Ray T Majuta PSDS City of Tucson Elect Plan Ck 9/27/09 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/08/2009 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 10/08/2009 | DELMA ROBEY | REJECT SHELF | Completed |