Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM03772
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/25/2007 | RBROOKS1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/25/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 09/25/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM03772 9/18/07 1. Add Panel R1 to Load Calculations Summary. 2. Please clarify the origin of the information: "AFC = 22,000". A 400A 120/208V TEP service would have 20,900A if the utility transformer were Pole type, and 27,800A if the utility transformer were Pad-mounted. Rework fault calculations if necessary. |
| 09/25/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |