Permit Number: T07CM03772
Parcel: 130053040

Address:
1909 E 36TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03772
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2007 MICHAEL ST. PAUL ZONING REVIEW Approved
09/18/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the size of the condensate drain piping per Section 307.2.2, IMC 2006, as amended by the City of Tucson.
09/18/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03772 9/18/07

1. Add Panel R1 to Load Calculations Summary.
09/18/2007 ROBERT SHERRY WATER REVIEW Approved
09/18/2007 JWILLIA5 BUILDING-COMMERCIAL REVIEW Denied 1) Provide 20% ADA Budget Calculations.
Per Roger Brooks
09/18/2007 PAUL MACHADO ENGINEERING REVIEW Approved
09/18/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Coordinate the backflow protection for the directly connected appliances with sheet A-3 and Section 603.0, UPC 2006, as amended by the City of Tucson. The appliances shall be individually protected.
09/18/2007 DAVE MANN FIRE REVIEW Approved
09/18/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/25/2007 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/25/2007 DELMA ROBEY OUT TO CUSTOMER Completed