Permit Number: T07CM03125
Parcel: 138240860

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM03125
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2008 ROBERT SHERRY WATER REVIEW Denied Comment not addressed. Provide a letter from Tucson Water confirming that the use of a 1" water meter will be allowed for this project (79 fixture units equates to a demand of 38 GPM)
02/04/2008 GERRY KOZIOL WWM REVIEW Denied 1:cope behavioral services inc. d.e.s. office bldg #3
2:needs to permit on-site private sewer-needs DEQ review & approval to construct on-sitte private sewer if over 3000 gal/day-needs manhole tap permit (5th floor review & 8th floor permit)-needs copy of on-site private sewer for base map update
02/05/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied The building plans cannot be approved without an approved site plan. Further review will be concidered once the site plan has been approved by all agencies.
02/12/2008 HEATHER THRALL ZONING REVIEW Denied The building plans can be further reviewed once the site plan has been approved by all agencies.

Please ensure all elevations show a building height from grade.

This building plan can be walked through the counter or with me in an appointment if you wish - once the site plan has been approved by all agencies. My email is Heather.Thrall@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
02/14/2008 DELMA ROBEY APPROVAL SHELF Completed
02/14/2008 DELMA ROBEY OUT TO CUSTOMER Completed
02/14/2008 DELMA ROBEY REJECT SHELF Completed