Permit Number: T07CM03125
Parcel: 138240860

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T07CM03125
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/10/2007 DAVE MANN FIRE REVIEW Approved
12/11/2007 ROBERT SHERRY WATER REVIEW Denied Provide a letter from Tucson Water confirming that the use of a 1" water meter will be allowed for this project (79 fixture units equates to a demand of 38 GPM)
12/12/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Impact Fee's Do Apply; West District; 11,755 Square Feet; $27,815.31
12/19/2007 GERRY KOZIOL WWM REVIEW Denied 1:cope behavioral services inc. d.e.s. office bldg #3
2:needs to permit on-site private sewer-needs DEQ review & approval to construct on-sitte private sewer if over 3000 gal/day-needs manhole tap permit (5th floor review & 8th floor permit)-needs copy of on-site private sewer for base map update
12/20/2007 HEATHER THRALL ZONING REVIEW Denied The building footprint has increased slightly in size on the building plans compared to what has been approved on the site plan. The site plan needs to be revised to show the change in width in the building, and how it may affect adjacent sidewalks could be an issue - hardly any room to move the sidewalk - it would be into the minimum required PAAL width. contact me at Heather.Thrall@tucsonaz.gov for an over the counter appointment for both the site plan revision and to possibly approve the building plans. Thank you.
12/28/2007 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: December 28, 2007
SUBJECT: New Office Building
TO: Reliable Permit
LOCATION: 1493 W Commerce Court, T15S, R13E, Section 15, Ward 1
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T07CM03125

RESUBMITTAL REQUIRED: Site Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed site plan for the above referenced property. Engineering Division does not recommend approval of the site plan at this time. Please address the following review comments prior to the next submittal.

Please include a response letter to the comments along with the corrected copies of the Site Plan

Site Plan:

1. As per the Federal ADA requirements, all wheel chair ramps shall have the truncated domes instead of the standard grooves that are shown on COT SD 207. Aside from the Truncated Domes, all wheel chair ramps shall be constructed in accordance with COT SD 207. Call out COT detail in detail description. Provide detail for truncated domes at pedestrian crossings along right of way.
2. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10.
3. Provide dimensions for sidewalks.
4. Fully dimensioned loading space(s) and maneuvering area(s) per D.S. 2-02.2.1.14. DS Sec.2-02.2.1.A.14: Provide (label and dimension) the required onsite maneuvering area for the loading zone that is shown adjacent to the proposed building. Refer to AASHTO for the national standards for turning radii.
5. Provide estimated cut & fill quantities per D.S. 2-02.2.1.17 on the site plan.
6. DS Sec.2.02.2.1.A.16: Provide drainage arrows and locations of all concentration points. Specifically show roof down spout locations for proposed buildings at pedestrian circulation areas. A detail for the dimension of the proposed scuppers that are used for collecting onsite roof drainage at all pedestrian sidewalk is required, refer to City of Tucson details. Any scuppers proposed under the sidewalk will be designed and constructed to convey the 10-year flood flow. Provide a drainage statement showing scupper calculations that demonstrate that the 10-year flood flow is contained under the sidewalk. Clarify in note 13 the reference to detail. There is no a sheet provided. If 7/x1.3 is the appropriate detail please revise accordingly.
7. DS Sec. 2-05.2.4.H.2: Provide the right-of-way (ROW) recordation information for Renaissance Drive.
8. Dimension from street monument lines to existing proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21. See attached paving plan information and modify dimensions accordingly.
9. Provide contour interval on site plan.
10. Show site plan activity number in the lower right hand corner of each sheet per D.S. 2-02.2.1.29.
11. Provide detail for trash enclosures and see verify that enclosures meet minimum requirements per City of Tucson Development Standard No. 6-01.0 Solid Waste Disposal (Refuse). See detail attached to sheet x1.3 of redlines for reference.
12. DS Sec.2-02.2.1.A.32: Label and show the maneuverability for refuse vehicles in plan view at the proposed refuse container location. In addition, depict 14' X 40' clear approach.
13. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
14. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the D/W, if applicable.
15. The Site Plan is currently in review. Any changes made to the Site Plan must be reflected on the Grading Plan. The Site Plan and Grading Plan must match.
16. DS Sec.2-02.2.1.A.8: Provide typical parking space detail for parking areas. Provide site plan parking dimensions, note and parking details for both standard and handicap parking, together with access thereto. See DS Sec. 3-05.2.0.B.1 for minimum parking standards.
17. Verify that keynote 7 located within the building is correct.

If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax

Final Status

Task End Date Reviewer's Name Type of Review Description
01/02/2008 VFLORES1 OUT TO CUSTOMER Completed