Permit Number: T07CM03125
Parcel: 138240860

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T07CM03125
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/28/2007 MARTIN BROWN FIRE REVIEW Approved
11/30/2007 HEATHER THRALL ZONING HC SITE REVIEW Approved
11/30/2007 HEATHER THRALL ZONING REVIEW Approved
12/07/2007 ANDREW CONNOR NPPO REVIEW Approved
12/07/2007 ANDREW CONNOR LANDSCAPE REVIEW Approved
12/12/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/28/2007 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: December 28, 2007
SUBJECT: New Office Building
TO: Reliable Permit
LOCATION: 1493 W Commerce Court, T15S, R13E, Section 15, Ward 1
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T07CM03125

RESUBMITTAL REQUIRED: Site Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed site plan for the above referenced property. Engineering Division does not recommend approval of the site plan at this time. Please address the following review comments prior to the next submittal.

Please include a response letter to the comments along with the corrected copies of the Site Plan

Site Plan:

1. As per the Federal ADA requirements, all wheel chair ramps shall have the truncated domes instead of the standard grooves that are shown on COT SD 207. Aside from the Truncated Domes, all wheel chair ramps shall be constructed in accordance with COT SD 207. Call out COT detail in detail description. Provide detail for truncated domes at pedestrian crossings along right of way.
2. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10.
3. Provide dimensions for sidewalks.
4. Fully dimensioned loading space(s) and maneuvering area(s) per D.S. 2-02.2.1.14. DS Sec.2-02.2.1.A.14: Provide (label and dimension) the required onsite maneuvering area for the loading zone that is shown adjacent to the proposed building. Refer to AASHTO for the national standards for turning radii.
5. Provide estimated cut & fill quantities per D.S. 2-02.2.1.17 on the site plan.
6. DS Sec.2.02.2.1.A.16: Provide drainage arrows and locations of all concentration points. Specifically show roof down spout locations for proposed buildings at pedestrian circulation areas. A detail for the dimension of the proposed scuppers that are used for collecting onsite roof drainage at all pedestrian sidewalk is required, refer to City of Tucson details. Any scuppers proposed under the sidewalk will be designed and constructed to convey the 10-year flood flow. Provide a drainage statement showing scupper calculations that demonstrate that the 10-year flood flow is contained under the sidewalk. Clarify in note 13 the reference to detail. There is no a sheet provided. If 7/x1.3 is the appropriate detail please revise accordingly.
7. DS Sec. 2-05.2.4.H.2: Provide the right-of-way (ROW) recordation information for Renaissance Drive.
8. Dimension from street monument lines to existing proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21. See attached paving plan information and modify dimensions accordingly.
9. Provide contour interval on site plan.
10. Show site plan activity number in the lower right hand corner of each sheet per D.S. 2-02.2.1.29.
11. Provide detail for trash enclosures and see verify that enclosures meet minimum requirements per City of Tucson Development Standard No. 6-01.0 Solid Waste Disposal (Refuse). See detail attached to sheet x1.3 of redlines for reference.
12. DS Sec.2-02.2.1.A.32: Label and show the maneuverability for refuse vehicles in plan view at the proposed refuse container location. In addition, depict 14' X 40' clear approach.
13. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
14. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the D/W, if applicable.
15. The Site Plan is currently in review. Any changes made to the Site Plan must be reflected on the Grading Plan. The Site Plan and Grading Plan must match.
16. DS Sec.2-02.2.1.A.8: Provide typical parking space detail for parking areas. Provide site plan parking dimensions, note and parking details for both standard and handicap parking, together with access thereto. See DS Sec. 3-05.2.0.B.1 for minimum parking standards.
17. Verify that keynote 7 located within the building is correct.

If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax