Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T06CM01707
Parcel: 12709011P

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T06CM01707
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM01707 11/14/06

1. Account for continuous loading on panel schedule calculations.
2. Correct the service load tally.
11/14/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide information to show how the water temperature will be limited to 110 degrees Fahrenheit. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/15/2006 CINDY AGUILAR APPROVAL SHELF Completed
11/15/2006 CINDY AGUILAR OUT TO CUSTOMER Completed