Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM01707 11/14/06

1. Account for continuous loading on panel schedule calculations.
2. Correct the service load tally.
11/14/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide information to show how the water temperature will be limited to 110 degrees Fahrenheit. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.