Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T06CM01707
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/14/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM01707 11/14/06 1. Account for continuous loading on panel schedule calculations. 2. Correct the service load tally. |
| 11/14/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide information to show how the water temperature will be limited to 110 degrees Fahrenheit. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/15/2006 | CINDY AGUILAR | APPROVAL SHELF | Completed |
| 11/15/2006 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |