Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM01707
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/30/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 03/30/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how recirculation of air from the restrooms is to be prevented. Reference section 403.2, IMC 2003. 2. Provide balancing information for the 3 rooftop units so that the ventilation calculations can be evaluated. Reference Section 403.3.2, IMC 2003. |
| 03/30/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE SERVICE SINK 2) WATER FOUNTAIN OR SUBSTITUTE WITH WATER COOLER THAT IS SHOWN ON DRAWINGS. 3) PROVIDE WALL SECTION |
| 03/30/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/30/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/12/2006 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 04/12/2006 | GBONILL1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 04/12/2006 | GBONILL1 | ENGINEERING | REVIEW | Needs Review | |
| 04/12/2006 | GBONILL1 | PLUMBING-COMMERCIAL | REVIEW | Denied |