Permit Number: T06CM01707
Parcel: 12709011P

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM01707
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/30/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
03/30/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how recirculation of air from the restrooms is to be prevented. Reference section 403.2, IMC 2003.
2. Provide balancing information for the 3 rooftop units so that the ventilation calculations can be evaluated. Reference Section 403.3.2, IMC 2003.
03/30/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE SERVICE SINK
2) WATER FOUNTAIN OR SUBSTITUTE WITH WATER COOLER THAT IS SHOWN ON DRAWINGS.
3) PROVIDE WALL SECTION
03/30/2006 ROBERT SHERRY WATER REVIEW Approved
03/30/2006 MARTIN BROWN FIRE REVIEW Approved
04/12/2006 GBONILL1 WWM REVIEW Needs Review
04/12/2006 GBONILL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
04/12/2006 GBONILL1 ENGINEERING REVIEW Needs Review
04/12/2006 GBONILL1 PLUMBING-COMMERCIAL REVIEW Denied