Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: DP19-0125
Parcel: 11706077R

Address:
211 N 4TH AV

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - DP19-0125
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/25/2022 STEVE SHIELDS ZONING REVIEW Approved
05/25/2022 SBEASLE1 ENGINEERING REVIEW Approved Engineering for this revision review was approved by Loren Makus during the recent OK to Submit.
05/26/2022 FRANK PODGORSKI HPZ ADVISORY BOARD HPZ ADVISORY BOARD DATE Completed Per our conversation, Historic does not need to review the plans for this revision. They are minimal and do not impact the overall design.

If you have any questions, please let me know.

Thanks!

Jodie Brown, AICP
Historic Preservation Officer
520.837.6968
06/02/2022 NMARTEL1 DESIGN PROFESSIONAL REVIEW Approved
06/03/2022 AWARNER1 LANDSCAPE REVIEW Approved
06/09/2022 JPEELDA1 FIRE REVIEW Reqs Change Buildings that exceed 30' in height shall comply with IFC 2018, Appendix D, D105.2 - D105.4 please provide a dedicated FP sheet that will show this information. Note it does state one entire side of the building. On your plans you shall show the side for the building and add a note that in these areas, awning, canopies and or solar shall never be installed. Fire Department Aerial Access lane shall also show fire lane signs.

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@tucsonaz.gov
520-837-7033Fire Plans Examiner
07/01/2022 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change Email from: COTDSDPermits
to: Jason Morse
Fri 7/1/2022 1:44 PM

REVISION REVIEW NOTICE
Returned for corrections, DP19-0125

Project Description: Site/Grading/SWPPP/FUP - Partners on Fourth PAD, new mixed-use 13-story building.

REVISION FEES DUE: $ 165.00 (extra review time by Fire Dept.)
** See Online Payment Instructions attached **

VIEW the review comments and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

YOUR NEXT STEPS: Submit documents to the Filedrop
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application"
1) Comment Response Letter (your response to
the reviewer's Requires changes comments)
2) Plan Set (or individual sheets)
3) Any other items/documents requested by review staff

Thank you.
Sharon Beasley, Certified Permit Technician

City of Tucson, Planning & Development Services Dept.
Email: COTDSDpermits@TucsonAz.gov
(for development packages, land splits, Thursday Presubmittal meetings)
Email: PDSDinquiries@TucsonAz.gov
(for building permits)
07/01/2022 SBEASLE1 UTILITIES TUCSON ELECTRIC POWER Approved email from: TEP-DEVREV <TEPDEVREV@tep.com>
to: CDRC
Fri 7/1/2022 11:22 AM

Tucson Electric Power Co. (TEP) has reviewed, and plans received, April 29th 2022 for 211 N 4TH AV and has no objections.

Costs for removing or relocating existing TEP facilities will be billable to the developer. A Preliminary electrical design is in process. The customer is responsible for compliance with City Ordinances. Please note jurisdictional permit for any work on a public road right of way where applicable.
Easements are required for TEP facilities if not appropriately recorded on the final subdivision plat. They will need to be obtained by separate instrument.

If there are any questions, don't hesitate to contact Land Resources at tepdevrev@tep.com.

Tucson Electric Power Co.
Land Resources Department