Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: DP13-0239
Parcel: 141383140

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW

Permit Number - DP13-0239
Review Name: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2014 CPIERCE1 START PLANS SUBMITTED Completed
03/27/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
04/02/2014 JANE DUARTE COT NON-DSD PARKS & RECREATION Approved Hi Trish,

My comments have been adequately addressed on the revised Tentative Plat. Please mark the Parks and Recreation Review Status as "Approved".

Thanks,
Howard

Howard B. Dutt, ASLA
Landscape Architect
Tucson Parks & Recreation
(520) 837-8040
Fax: (520) 791-4008
Howard.Dutt@tucsonaz.gov
04/11/2014 RONALD BROWN ZONING HC REVIEW Approved
04/16/2014 LAITH ALSHAMI ENGINEERING REVIEW Approv-Cond Laith Alshami, Engineering and Floodpain Review, 04/16/2014,

SUBJECT: Sierra Morado Unit 3
DP13-0239, T15S, R15E, SECTION 12

RECEIVED: Development Plan Package and Drainage Report on March 18th, 2014

The subject project has been reviewed. The Drainage Report and Development Package are recommended for a conditional approval, pertaining to Engineering and Floodplain Review, subject to the following:

1. Revise the Drainage Report and General Notes #18 and #19 to clarify that the areas, where lots 129-131, 153, 157, 158, 162, 163 and 168 are located, are impacted by the regulatory floodplain. Those areas will be removed from the floodplain area once a fill is installed and a LOMRF is approved. The fill will require a floodplain use permit. Once the fill is installed and the LOMRF is approved, the lots within the affected areas will not require separate floodplain use permits and elevation certificates.

If you have any questions, I can be reached at 837-4933 or Laith.Alshami@tucsonaz.gov

RESUBMITTAL REQUIRED: Revised Development Plan Package and Drainage Report
04/17/2014 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approv-Cond The above listed review has been completed.

Minor revisisions are required by Engineering. Please make the necessary changes, add the revised sheets to the plan sets at PDSD prior to final approval of the plans.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/21/2014 SHANAE POWELL OUT TO CUSTOMER Completed