Plan Number: TR-FTTP-0826-00010
Parcel: 13623005K

Address:
2762 S KOLB RD

Review Status: Requires Resubmit

Review Details: RIGHT OF WAY REVIEW v.1

Plan Number - TR-FTTP-0826-00010
Review Name: RIGHT OF WAY REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
Public Notice PENDING ASSIGNMENT
ROW Engineering Review Standard REQUIRES RESUBMIT TCP: add 1. Set up hours, 2. Stamp
Design plan: 1. add depth to method of work 2. add note "Prior to construction, the Contractor shall contact Arizona 811 and field verify the horizontal and vertical location, size, and depth of all existing utilities that may conflict with or be crossed by the proposed installation. Verification shall be completed prior to excavation, boring, or installation within the affected area. The Contractor shall adjust the proposed installation as necessary to avoid conflicts and shall maintain all required horizontal and vertical separations from existing utilities in accordance with City of Tucson requirements, utility-owner requirements, and the approved permit. Any field condition that prevents the required separation from being maintained shall be reported to the Engineer/Owner and City for resolution prior to proceeding with the affected work." when crossing utilities 12" or deeper and a plan in profile cannot be provided.